6 DetaileddescriptionsofI/Omodules | Digital output module UR20-16DO-P-PLC-INT
195Manual u-remote1432790000/08/12.2015
Technical data UR20-16DO-P-PLC-INT (Order No. 1315270000)
System data
Data
Process, parameter and diagnostic data depend on the coupler used,
see the table in Section 4.10.
Interface
u-remote system bus
System bus transfer rate
48 Mbps
Outputs
Number
16
Type
P-switching
Type of load
ohmic, inductive, lamp load
Response time
low » high max. 100 µs; high » low max. 250 µs
Max. output current
per channel 0.5A
per module 8 A (2 A with power supply via a at ribbon
cable)
Breaking energy (inductive)
150mJ per channel
Switching frequency
Ohmic load (min. 47 Ω) 1kHz
Inductive load (DC 13) 0.2Hz without free-wheeling diode
1kHz with suitable free-wheeling diode
Lamp load (12W) 1kHz
Actuator connection
PLC interface unit
Short-circuit-proof
yes
Protective circuit
Constant current with thermal switch-off and automatic restart
Response time of the current limiting circuit
<100µs
Module diagnosis
yes
Individual channel diagnosis
no
Reactionless
yes
Can be used with PF-O-xDI-SIL
yes
Supply
Supply voltage
24V DC +20 %/-15 %
Current consumption from system current path I
SYS
8mA
Current consumption from output current path I
OUT
25mA + load, power supply via feed-in plug or PLC connection
Connection data
Type of connection
“PUSH IN”
Line connection cross-section
Single-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
Fine-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
I/O connector
20-pole PLC connection
General data
Weight (operational status)
82g
For additional general data, see Section 3.4