User manual
6 DetaileddescriptionsofI/Omodules | Digital input module UR20-16DI-N-PLC-INT
163Manual u-remote1432790000/08/12.2015
Technical data UR20-16DI-N-PLC-INT (Order No. 1315400000)
System data
Data
Process and diagnostic data depend on the coupler used,
see the table in Section 4.10.
Interface
u-remote system bus
System bus transfer rate
48 Mbps
Inputs
Number
16
Input type
N-switching, comparable to Type1 and Type3 sensors as per IEC 61131-2
Input filter
Input delay 3ms
Low input voltage
>- 5V referred to +24V of the input power supply U
IN
High input voltage
<- 11V referred to +24V of the input power supply U
IN
Sensor supply
External
Sensor connection
PLC interface unit
Reverse polarity protection
yes
Module diagnosis
yes
Individual channel diagnosis
no
Supply
Supply voltage
24V DC +20 %/-15 %
Current consumption from system current path I
SYS
8mA
Current consumption
<15mA, power supply via feed-in plug or PLC connection
General data
Weight (operational status)
82 g
For additional general data, see Section 3.4