3 Systemoverview | General technical data for I/O modules
15Manual u-remote1432790000/08/12.2015
3.4 General technical data for I/O modules
Type of connection
“PUSH IN” Single-wired, ne-wired
Conductor cross-section 0.14 – 1.5mm
2
(AWG 16 – 26)
IDC (modules UR20-...-HD) Single-wired, ne-wired
Conductor cross-section 0.14 – 0.35mm
2
(AWG 22 – 26)
Dimensions
Height 120.0mm / 4.72" (with release lever: 128.0mm / 5.04")
Width 11.5mm / 0.45"
Depth 76.0mm / 2.99"
Protection class (DIN EN 60529)
IP 20
FlammabilityratingUL94
V-0
Temperature data
Operation
-20°C
... +60 °C / - 4 ... +140°F
Storage, transport
-40°C
... +85 °C / - 40 ... +185°F
Humidity
Operation, storage, transport 5 % to 95 %, non-condensing as per IEC 61131-2
Air pressure
Operation ≥ 795 hPa (altitude ≤ 2000m) as per IEC 61131-2
Storage, transport ≥ 700 hPa (altitude ≤ 3000m) as per IEC 61131-2
Vibration resistance
5Hz ≤ f ≤ 8.4Hz: 3.5-mm amplitude as per IEC 60068-2-6
8.4Hz ≤ f ≤ 150Hz: 1-g acceleration as per IEC 60068-2-6
Shock resistance
15 g over 11ms, half sinewave, as per IEC 60068-2-27
Potential isolation
Test voltage max. 28.8V within one channel
500V DC eld/system
Pollution severity level 2
Overvoltage category II
Approvals and Standards
cULus UL 508
Potentially explosive atmosphere Zone 2* ATEX Directive 94/9/EC
EMC IEC 61000
(partial standards as per the requirements of IEC 61131-2)
Explosion protection IEC60079-0:2012, IEC60079-15:2010, EN60079-0:2012,
EN60079-15:2010
PLC IEC 61131-2
* unless otherwise noted within the product-specific technical data.