6 DetaileddescriptionsofI/Omodules| Digital input module with time stamp UR20-2DI-P-TS
136 1432790000/08/12.2015Manual u-remote
Diagnostic data UR20-2DI-P-TS
Name Bytes Bit Description Default
Error indicator 0
0 Module error
1 Internal error
2 External error
3 Channel error 0
4 Error
5 Reserved 0
6 Reserved 0
7 Parameter error
Module type 1
0
Module Type 0x0F
1
2
3
4 Reserved 0
5 Reserved 0
6 Reserved 0
7 Reserved 0
Error byte 2 2 0 – 7 Reserved 0
Error byte 3 3
0 – 2 Reserved 0
3 Internal diagnostic FIFO full 0
4 – 7 Reserved 0
Channel type 4
0 – 6 Channel type 0x70
7 Reserved 0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
0
Number of
channels
6
Number of similar channels per
module
2
Channel error 7 – 10 0 – 31 Reserved 0
Channel 0 error
to
Channel 31 error
11
to
42
0 – 7 Reserved 0
Time stamp 43 – 46 time stamp [µs] (32bit)
Process data
1)
inputs UR20-2DI-P-TS
Byte Format Name Remark
IB0 Byte Input image 1
Bit0 = DI0 ... Bit1 = DI1,
Bit2 ... 7 reserved
IB1 Byte Running number 1 0 ... 127 rotating
IB2
Wort Time stamp 1 0 ... 65535µs rotating
IB3
IB4 Byte Input image 2
IB5 Byte Running number 2
IB6
Wort Time stamp 2
IB7
IB8 Byte Input image 3
IB9 Byte Running number 3
IB10
Wort Time stamp 3
IB11
… … …
IB56 Byte Input image 15
IB57 Byte Running number 15
IB58
Wort Time stamp 15
IB59
1) Internal process data mapping with data format “Standard”. Depending on
the eldbus specication and the data format of the communicating eldbus
components the bytes and/or words can be reversed during data transfer.