User manual
6 DetaileddescriptionsofI/Omodules| Digital input module UR20-8DI-P-2W
116 1432790000/08/12.2015Manual u-remote
Diagnostic data UR20-8DI-P-2W
Name Byte Bit Description Default
Error indicator 0
0 Module error
1 Internal error
2 External error
3 Channel error 0
4 Error
5 Reserved 0
6 Reserved 0
7 Parameter error
Module type 1
0
Module Type 0x0F
1
2
3
4 Reserved 0
5 Reserved 0
6 Reserved 0
7 Reserved 0
Error byte 2 2 0 ... 7 Reserved 0
Error byte 3 3
0 ... 2 Reserved 0
3 Internal diagnostic FIFO full 0
4 ... 7 Reserved 0
Channel type 4
0 ... 6 Channel type 0x70
7 Reserved 0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
0
Number of
channels
6
Number of similar channels per
module
8
Channel error 7 ... 10 0 ... 31 Reserved 0
Channel 0 error
to
Channel 31 error
11
...
42
0 ... 7 Reserved 0
Time stamp 43-46 time stamp [µs] (32bit)
Process data inputs UR20-8DI-P-2W
Byte Bit Description
IB0
IX0.0 DI0
IX0.1 DI1
IX0.2 DI2
IX0.3 DI3
IX0.4 DI4
IX0.5 DI5
IX0.6 DI6
IX0.7 DI7