User manual

5 Detailed descriptions of the eldbus coupler | CANopen eldbus coupler UR20-FBC-CAN
102 1432790000/08/12.2015Manual u-remote
1
5
6
9
X1
24 V DC OUT
24 V DC OUT
GND OUT
GND OUT
24 V DC IN
24 V DC IN
GND IN
GND IN
CAN
CANL 2
GND 3
Shield 5
GND 6
CANH 7
Connection diagram UR20-FBC-CAN
µC
8x
USB
DC
DC
System
bus
U
SYS
U
IN
U
OUT
Sub-D
System
bus
System
bus
U
SYS
U
IN
U
IN
U
OUT
U
OUT
24 V/10 A Input
24 V/10 A Output
Internal from the control card
Block diagram UR20-FBC-CAN
ATTENTION
Risk of material damage!
In the case of a maximum power supply of >8 A and a
maximum temperature of > +55 °C, all four contacts must
be connected with 1.5mm² wiring!
Sub-D pin assignment
Pin Signal Description
1 not connected
2 CANL CAN– bus line
3 GND Ground
4 not connected
5 SHIELD Cable shield
6 GND Ground
7 CANH CAN+ bus line
8 not connected
9 not connected
Case SHIELD Cable shield