Datasheet
Datenblatt
ACT20M
ACT20M-AI-AO-S
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technische Daten
Erstellungs-Datum December 17, 2013 12:58:09 PM CET
Katalogstand xx.xx.xxxx / Technische Änderungen vorbehalten 2
Dimensions and weights
Width 6.1 mm
Height 112.5 mm
Depth 114.3 mm
Net weight 80 g
Temperatures
Humidity 40 °C / 93 % rel. humidity,
no condensation
Operating temperature
-25 °C...+70 °C
Ambient temperature -25 °C...+70 °C
Storage temperature -40 °C...+85 °C
Probability of failure
MTBF 231 Years
Input
Sensor supply > 17 V DC at 20 mA
Supply voltage 24 V DC ± 30 %
Voltage drop, current input <1,5 V
Input frequency 100 Hz
Input current 0...20 mA, 4…20mA
Input resistance, voltage >500 kΩ
Temperature input range Configurable
Voltage drop
<1,5 V
Input voltage 0(2)…10 V, 0(1)…5 V
Output
Cut-off frequency (-3 dB) 100 Hz
load impedance voltage ≥ 10 kΩ
Number of outputs 1
load impedance current ≤ 600 Ω, @ max 23mA
Output voltage, note adjustable, 0(2)...10 V,
0(1)...5 V
Output current adjustable, 0...20 mA,
4...20 mA
General data
Accuracy < 0.05 % of measuring
range
Configuration
DIP switch
Galvanic isolation 3-way isolator
Mounting rail TS 35
Power consumption, max. 1.2 W
Power consumption, typ. 400 mW
Step response time ≤ 7 ms
Supply voltage 24 V DC ± 30 %
Temperature coefficient ≤ 0.01 % / °C
Type of connection Screw connection
Insulation coordination
EMC standards EN 61326-1
Galvanic isolation 3-way isolator
Insulation voltage 2.5 kV
eff
Pollution severity
2
Rated voltage
300 V
eff
Standards DIN EN 61010-1, DIN EN
60079, DIN EN 61326-1
Surge voltage category II
Ratings IECEx/ATEX
Certificate No. (ATEX) KEMA10ATEX0183X
Certificate No. (IECEX) IECEXKEM10.0090X
Classifications
ETIM 3.0 EC002479
eClass 6.2
27-21-01-20
eClass 7.1 27-21-01-20