Technical data

5 Troubleshooting Thermo 230 / 231 / 300 / 301 / 350
502
Heater operation stops because heat exchangers
connected do not dissipate enough heat.
Rate of flow too low, because
air in heater, in heat exchangers or in system
sections.
cocks (flow regulator) throttled, contaminated or
closed.
contamination in system, e.g. in areas of restricted
flow.
circulation pump rate of delivery insufficient (air in
pump housing).
wrong sense of rotation – check wiring colors
(black + / brown –).
not enough anti-freeze.
excessive system resistance (especially high when
cold).
circulation pump defective.
Heat exchanger dissipate not enough heat,
because
air in heat exchangers or in system sections.
contaminated heat exchanger surfaces (external).
insufficient air intake or exit.
fan: rate of delivery low / wrong sense of rotation /
resistance too high.
too much anti-freeze.
heat exchanger of too low capacity.
Rough calculation of rate of flow
heat flow [kW] acc. to ident. label
Rate of flow in [l/h] = x 860
temperature difference t in [K] or [°C]
measured between heater water inlet and outlet
(e.g. with contact thermometer)
Fault in fuel supply
No fuel delivery to heater. fuel tank empty.
kinked, closed, contaminated or leaking lines.
paraffin deposits or water captured in fuel filter or fuel
lines.
vent in tank clogged.
fuel lines interchanged.
fuel filter contaminated.
fuel screen in pump contaminated.
Fig. 501 General Fault Symptoms (Sheet 2 of 3)
Symptom Probable Cause