Specifications
Operation / Installation Manual – FCF 5000, 9000, 12000, 16000, 24000 
Page 25 
Troubleshooting 
FAULT  POSSIBLE REASON  CORRECTION 
Will not start  Air conditioning circuit breaker is off  Turn circuit breaker on at ship's panel, 
See control operation section in this manual. 
Display control is not turned on.  Check wiring Diagram and correct if necessary. 
Fuse is broken  Replaced with a new fuse. (3.15 AL 250V) 
Incorrect wiring at terminal strip. 
Disconnect power supply and open electric box, check 
wiring diagram, correct if necessary, 
Push-on butt connectors pulled apart during 
installation. 
Check power source (shore/generator) for proper voltage. 
Input line voltage is insufficient,  Check wiring and terminals for proper sizes and 
connections. 
Fan not 
running. 
Check your specific control Troubleshooting section   
No cooling or 
heating 
Temperature set point is above (in cooling) or below 
(in heating) ambient temperature 
Lower or raise set point. 
Obstructed seawater flow.  Clean seawater strainer. Check for obstructions at speed 
scoop thru-hull inlet. Check for a good steady flow from the 
overboard discharge. 
Seawater pump maybe air-locked, 
Remove hose from pump discharge to purge air from lin
e 
Refrigerant gas leaked.  Check air conditioning unit for refrigerant oil leakage, call 
service technician. 
Seawater temperature too high for cooling or too low 
for heating. 
Seawater temperature will directly affect the air conditioning 
unit’s efficiency. This air conditioning unit can effectively cool 
your boat in water temperature up to 90
0
F and heat (if 
reverse cycle option is installed) in water as low as 40
o
F. 
Coil is iced (in cooling)  See below 
Fan is not running.  See below 
Pressure switch or thermal overload opened.  Check your specific control troubleshooting section. 
No Heating  Reversing valve may be stuck.  Tap reversing valve lightly with rubber mallet while unit is in 
heat mode, call for service if the problem cannot be solved. 