User's Manual

QC Guide of Active Hub
Jul. 13
20
3. Testing Active Hub on TSU Networks using OUT port:
Now remove the Cable from the “IN” of the Active Hub and put it into “OUT” of Active Hub and Test the Active
Hub by following the procedure as described in section VII, we will get same result.
4. Test of Termination DIP Switch
A) Make sure Termination DIP switch is Enable. Now connect the RJ45 connector into “IN” of the Active Hub Port
as shown in figure.
Connect the cable on IN port of the Active Hub as shown below.
Then measure the resistance between Pin 3 and Pin 6 , the resistor value be 120 ohms as shown in the figure.
Use opposite
configuration as Dip
switch is now bottom
actuated.