Instruction manual
17
To select the second menu, press and release the Return/Enter button.
This menu will display 3 functions:
Power Test
Leakage Test
RCD Test
To enter the RCD menu press and release the F3 button.
RCD Tests
Time Test
Ramp Test
Exit
Press F1 to select the time test.
Trip Time Testing: This principal is designed to trip RCD devices at a fixed current and to determine the trip time of the RCD
device.
This function is factory set to 30mA for fast testing the user can set the current to X0.5, X1.0, X 5 using the RCD Multiplier.
I.E. 30mA X 0.5 =15mA
30mA X 1.0 = 30mA (this also is effective on any set test current of the RCD tester from 5mA to max 500mA output.)
30mA X 5.0 = 150mA
These tests should result in no-trip, trip & fast trip times respectively.
F1 - 0 deg
This is the positive half of the mains supply cycle. (50HZ Aust/NZ). Press F1 – The preset mA test current
will then be used in the following test and begin the trip test from the positive half of the sine wave
F2 - 180 deg
This is the negative half of the mains cycle, (50HZ Aus/NZ). Press F2 - The preset mA test will then be
used in the following test and begin the trip test in the negative half of the sine wave