Specifications
RT9 Powershelf Rectifier Technologies
158-1806-01.doc
28 2-Mar-06
Alarm Name Comments LED
Cell %dev Low One or more cells being monitored by BCM is too low % deviation from
the mean battery cell voltage
A
Range SMR SMR parameter range error. MiniCSU-3 could not overwrite values A
Site Monitor Alarm present from the site monitor module. See site monitor menu for
details of alarm channel.
A
Battery Disch Batteries are discharging A
Disch Tst Fail Battery discharge test failed to reach a programmed end point A
Bat Disch Low Alarm flags only if the system voltage falls below Discharge Alarm level
while the battery is discharging
A
Lo Electrolyte Alarm generated for NiCad batteries using special sensor and software A
SMR Comms Fail One or more of SMRs are not responding A
Amb Temp High Ambient temperature higher than preset limit A
Batt Temp High Battery temperature higher than preset limit A
Batt Temp Sens Battery temperature sensor not connected or failure A
Batt I-Limit Battery charging current is being limited to preset value A
Bat Sym Alarm Battery discharge currents from battery strings not sharing load equally A
Earth Leak Alarm Earth leakage current greater than the limit set A
Equalise System is in equalise mode A *
R = red LED on A = amber LED flashing * not flashing
5.2.4 User programmable relay functions
Units are shipped with factory default relay assignments (see below). The relay logic of
the default settings is contact closure on an active alarm. Relay functions can be re-
assigned only from a PC running monitoring program WinCSU-2 (either through the front
panel USB or remote communications port). Refer to WinCSU-2 Help for instructions.
Relay Default Assignments
1 2 3 4 5
Not Assigned Not Assigned HV Shutdown General Alarm SMR Shutdown
Customer Relay Assignments
(User to complete)