Cut Sheet

DELAY
PIR 50%
WALK
AUD. ALERT
RLY 1 MAN
RLY 2 MAN
VIS. ALERT
=ON =OFF
=Factory Setting
8
Auto On
Manual On
Relay 1 Mode
9
Auto On
Manual On
Relay 2 Mode
5
High
Low, 50%
PIR Sensitivity
7
Disabled
Enabled
Audible Alert
4
Disabled
Enabled
Walk-Through
9123456 78
Time
Delay
Walk-Through
ON
Relay 1 Mode
Relay 2 Mode
Audible Alerts
PIR Sensitivity
Visible
Alerts
Test/20 min
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
Service
5 minutes
123
Time Delay
Service bypasses occupancy
& light level functions. Control the
load manually using ON/OFF button.
6
Disabled
Enabled
Visible Alert
Ground
PW-203 PW-203
Junction BoxJunction Box
Black (Line)
Red (Load 1)
Brown (Load 2)
Blue (Line)
White (Neutral)
Yellow (Traveler)
Load 1
Load 2
1
2
120/277V 50/60Hz
White (Neutral)
Black (Line)
PIR
Coverage
7.5’
(2.2m)
15’
(4.5m)
20’
(6.1m)
35’
(10.6m)
Major motion
Minor motion
PIR Coverage
7.5’
(2.2m)
15’
(4.5m)
20’
(6.1m)
35’
(10.6m)
Major motion
Minor motion
4’
(1.2m)
20’
(6.1m)
35’
(10.6m
)
0
WWW.LEGRAND.US/WATTSTOPPER
Pub. No. 34603 Rev. 08/2016
120/277 VAC; 50/60 Hz
@
120 VAC, 0-800 W ballast or tungsten,1/6 hp
@
277 VAC, 0-1200 W ballast
Time delays: 5, 10, 15, 20, 25 or 30 minutes, walk-through,
test-mode
Coverage: Major motion 35’ x 30’
Minor motion 20’ x 15’
Sensitivity adjustment: PIR (high/low)
Dimensions: 2.73” x 1.76” x 1.83”
(69.3mm x 44.7mm x 46.5mm) L x W x D
UL and cUL listed
Five year warranty
Specifications
Controls & Settings
Product Controls DIP Switch Settings
Coverage & Wiring
Multi-way Bi-level Wiring Diagram Coverage Patterns
Ordering Information
DIP Switches
Detection LED
ON/OFF Buttons
PIR Lens
Catalog #
Color Voltage Load Rating
PW-203-W White
120/277 VAC; 50/60 Hz
@
120 VAC, 0-800 W ballast or tungsten,1/6 hp
@
277 VAC, 0-1200 W ballast
PW-203-LA Lt. Almond
PW-203-I Ivory
PW-203-G Gray
PW-203-B Black
Order wall plate separately.
For best performance in single location applications,
Wattstopper recommends using this sensor in spaces
no larger than 15’ x 12’. In multi-way applications,
each connected sensor expands the coverage area.