Cut Sheet

Conguration: Red LED
Load Status: Blue LED
Load On/Off
Conguration Button
6.5”
(165mm)
2.625”
(67mm)
6.5”
(165mm)
WWW.LEGRAND.US/WATTSTOPPER
Pub. No. 35704 Rev. 07/2016
Input/ouput voltage: 120VAC, 50/60Hz
Load ratings:
Ballast or incandescent: 20A
Motor load: 1Hp
Class 2 output to DLM local network: 24VDC,
250mA across 4 RJ45 ports
DLM local network parameters:
Maximum current: 800mA
Cat 5e cable: 150’ per device to 1,000’ max.
Up to 48 communicating devices
Up to 64 loads
Maximum 4 LMPB-100, LMPL-101 or LMRC-100 Series
Room Controllers
Operating conditions: for indoor use only;
32-158°F (0-70°C); 5-95% RH, non-condensing
UL (88T9) and cUL listed
FCC part 15 compliant
Five year warranty
Specifications
Controls & Mounting
Controls and Dimensions Mounting and Wiring
Connecting
Sample Connection Diagram for Bi-Level Lighting and Plug Load Control
Ordering Information
Load Rating
Catalog #
Description Voltage
Ballast(A) Incan(A) Motor
Class 2 Output
LMPL-201
Plug Load Controller 120VAC; 50/60Hz 20 20 1 Hp 24 VDC; 250 mA
Mount to 4” x 4” x 2 1/8”
deep electrical box.
J-Box
LMRC-212
LM-MSTP Wire
Segment Network
(linear topology twisted pair dataline)
LMPL-201
Plug Load
Room
Controller
Switch
Ceiling Mount
Sensor
LMBC-300
Network Bridge
Loads
1
2
LMRJ Cables
To
additional DLM
Local Networks
To
Segment Manager
or BAS
Plug DLM local network
together in any configuration
using Cat 5e cables with