Cut Sheet

DIGITAL LIGHTING MANAGEMENT
www.wattstopper.com | 800.879.8585
Dimensions &
Mounting
Specifications
• Inputvoltage:24VDCfromDLMnetwork
• Currentconsumption:20mA
• DLMlocalnetworkconnection:1RJ45portvia
RJ45plugandcoupler(included)
• LCDdisplayandpushbuttonsforsettingsensor
and system parameters
• Infrared(IR)transceiver
• Ultrasonicfrequency:40kHz
• Operatingconditions:forindooruseonly;
32-104°F (0-40°C); 5-95% RH, non-condensing
• ULandcULlisted
• FCCpart15compliant
• Fiveyearwarranty
Ordering
Information
Pub. No. 30202 rev. 11/2010
Sample Connection Diagram
Product Dimensions
Coverage Patterns
Occupancy Sensors
Controls &
Indicators
Catalog No. Color Description
LMDX-100
LMDX-100-U
White
White
Digital Dual Technology Corner Mount Occupancy Sensor
Digital Dual Technology Corner Mount Occupancy Sensor, ARRA-compliant
J-box
Wall
Mounting plate
and base
Occupancy
Sensor
Snug
Ring
Wall
Snug
Ring
Secure
Snug
Ring
Loose
Screw
30 ft.
30 ft.
Sensor
PIR
RETRIG
Up button
Down button
LCD
display
Feature button
Conguration
button
Blue LEDRed LED
Product Controls and Sensor Settings
Switch
LMDX-100
Corner Mount
Sensor
LMRJ Cables
Load
Line Voltage
Room
Controller
J-Box
1
Wiring
Coverage &
Placement
4.75”
(121mm)
3.0”
(76mm)
0.9”
(23mm)
3.9”
(99mm)
2.4”
(61mm)
2.4”
(61mm)
4.75”
(121mm)
Mount to a box or directly to a ceiling tile. Mounts
to 4” square box, j-boxes or octagonal boxes. See
installation instructions for more details.
Wall and Ceiling Mounting Options
Sensor Placement
Side view
10’
Top view
45’
13.71m
07 15’ 25’ 45’
PIR
coverage
45ft (13.71m)
Ultrasonic
coverage
28ft (8.53m)
Sensor Parameter Available Options Default Setting
Time Delay 1-30 min. (1min. increments) /Override 20 minutes
Walk Thru On/Off Off
PIR Sensitivity 10-100% (10% increments)/Off 90%
Ultrasonic Sensitivity 10-100% (10% increments)/Off 70%
Test Mode Activate Off
Detection Technology Ultrasonic/PIR/Both/Either Both
Retrigger Technology Ultrasonic/PIR/Both/Either Either
Plug DLM local network components
together in any configuration using
Cat5ecableswithRJ45connectors.