DESCRIPTION AND OPERATION
The HB350W-L3 occupancy sensors is designed for automatic lighting control in high bay wet location applications. The sensor is
modular and are made up of two parts, a Sensor Module (HB350W) and a Lens (L3). The sensor uses a set of DIP switches to set the
time delay and PIR sensitivity as explained on page 2. The HB350W-L3 provides a single load controlling relay.
INSTALLATION OVERVIEW
1. Review the ADJUSTMENTS section and complete any
necessary DIP switch setting changes.
2. Mount the sensor so the lens is below the edge of the fixture
and away from the lamps. Heat from the lamps could affect
the sensor operation.
Make sure that you have the appropriate accessories for the
sensor mounting configuration. (See Mounting Options.)
3. Assemble any necessary mounting accessories and attach
them to the sensor module. Make sure that the flying leads
from the sensor module cable are accessible inside the
fixture.
4. Connect the line voltage and load wires to the sensor leads
as shown in the applicable Wiring Diagram for the sensor
module.
Do not allow bare wire to show.
Make sure all connections are secure.
Check all gaskets for watertight fit.
5. Check sensor operation. Refer to the TESTING section.
6. Attach the Lens to the HB350W-L3 as shown in the sensor
assembly drawing.
SPECIFICATIONS
Voltages .................................................................. 120/277VAC,60Hz
Load Requirements
@120VAC, 60Hz .......................................0-800W ballast or tungsten
@277VAC, 60Hz ........................................................0-1200W ballast
@120VAC ................................................................................... 1/6 hp
Wiring cable .......... 3 or 4-conductor 18AWG stranded, UL Style 2517
Unit Dimensions ......................................... 4.08” diameter, 1.88” thick
Threaded nipple ..........................................0.81” diameter, 0.40” long
fits standard 1/2” electrical conduit fitting
Weight .................................................................. 0.28 lb (130 grams)
Material ............... Polycarbonate, UL94-5VA flame retardant material,
UV resistant, indoor use only,
minimum plastic wall thickness 2.5mm
Environment ................................................................ IP65 Compliant
Operating temperature ........................ -40°F (-40°C) to 131° F (55°C)
Storage temperature ............................ -40°F (-40°C) to 176°F (80°C)
Operating humidity ...............................5 to 95% RH, non-condensing
Maximum Dew Point ........................................................29°C (85°F)
US Patents: ..................................................5,640,113 and 5,804,991
CAUTION
TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE INSTALLING THE SENSOR.
HB350W (sensor module)
HBL3W (lens module)
Tightening ring
Sensor Assembly
DIP switches

Summary of content (4 pages)