Installation Manual
4
WIRING AND INSTALLATION
Cover plate
4” round
outdoor
junction-box
WHITE
BLACK
RED
NOTE: W
eather proof caulking may
be required around junction box
and cover plate to provide a
weatherproof seal in some
installations.
Gasket
IMPORTANT! Thread wires
through gasket before connecting
to Controlled Loads
Isolated Relay Wires (N/O, COMMON, N/C)
(EW-200 models only)
Attach cover plate
assembly and gasket to
the junction box with 4
screws and screw
covers (supplied)
IMPORTANT! Make sure
that the gasket seats
properly when attaching
the cover plate
Wire connections when attaching lamp holders (Isolated relay wires not shown)
4” round
outdoor
junction-box
WHITE
BLACK
RED
Cover plate
Lamp Holder
(CANLET lamp holder shown)
Gasket
IMPORTANT! Thread wires through
gasket before connecting to additional
Controlled Loads (optional)
Attach cover plate assembly
and gasket to the junction
box with 4 screws and screw
covers (supplied)
IMPORTANT! Make sure that the
gasket seats properly when
attaching the cover plate
NOTE: W
eather proof caulking may
be required around junction box
and cover plate to provide a
weatherproof seal in some
installations.
Wire connections for sensor
WARNING:
WHEN USED WITH LAMP HOLDERS
THE LAMPS NEED TO BE 1/2”
OR GREATER FROM THE SENSOR.
CAUTION: TURN POWER OFF AT THE
CIRCUIT BREAKER BEFORE INSTALLING
SENSOR.SENSOR MUST BE INSTALLED
BY QUALIFIED PERSONNEL ONLY.
WIRING AND INSTALLATION
Wire the sensor as shown:
• BLACK wire from sensor to line voltage.
• WHITE wire from sensor to Neutral.
• RED wire is connected to lighting loads, if used, as shown (see diagram above and below), not to exceed load rating (see
Specifications, front cover).
• Isolated Relay (EW-200 models only. See Specifications, front cover, for rating).
Connect the wires necessary to the application that requires this output.
▸ ORANGE (Common) (must be used for proper operation).
▸ GREEN (Normally Closed) (Open when occupancy is detected).
▸ YELLOW (Normally Open) (Closed when occupancy is detected).
NOTE: When power is restored to the sensor, the lights will turn on. If no motion is detected by the sensor, the lights will remain on for
approximately one minute and then turn off. (See Security Override).