Manual
Series TR
Transition Risers
Sizes: 4" – 10" (100-250mm)
Series TR Transition Risers are used to connect the main fire
supply to the building overhead fire system. The fitting passes
under the foundation without joints and extends up through the
floor. Provided with installation tabs, the unit has a CIPS (Cast
Iron Pipe Size) coupler for easy connection to the underground
supply (AWWA C900 PVC and Ductile Iron Pipe) and industry
standard grooved-end connection (AWWA C606) on the building
side for easy connection to the overhead fire sprinkler system.
Watts Transition Risers are precision engineered and manu-
factured to provide exceptional reliability and reduce instal-
lation time & labor costs associated with field assembly. In
accordance with NFPA 24-2007, the UL and FM approved
Transition Risers replace numerous fittings, elbows & spools
and reduces the possibility of leaks or failure in comparison to
traditional installation methods and materials. Factory tested
integrity ensures the highest quality installation. The use of
stainless steel significantly increases the reliability and life of the
riser.
Features
•Costsavings
•Corrosionresistantstainlesssteelconstruction,type304
•Easeofinstallationandlightweightallowonepersonto
position and handle the riser
•Minimalsitepreparation;jointrestraintone-piececonstruc-
tionreducestimeandlabor;nomissingparts,noleaks;easily
identifiable for approvals
•IncludesTestCapandCoupler
•ULandFMapproved
•Sizes:availablein4"–10"(100-250mm)withvarious
lengths to meet all local requirements
•DesignedtomeetNFPA24-2007Section10.6.5
•AWWAC900Inlet/DIP
•AWWAC606Outlet
Specification
Transition Riser shall be installed as indicated on the plans.
Riser shall be composed of a single extended 90 degree fit-
tingoffabricated304stainlesssteeltubing,maximumworking
pressure200psi(14bar).Thefittingshallhaveagrooved-end
connection on the outlet (building) side and a CIPS coupler on
the inlet (underground) side. The grooved end shall include a
Coupler and Cap to facilitate testing of the underground piping.
The Transition Riser shall be a Watts Series TR.
For Fire Protection Applications
ES-TR
Job Name
––––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
––––––––––––––––––––––––––––––––––––––––––
Approval
––––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’sP.O.No.
–––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
–––––––––––––––––––––––––––––––––––––––––
IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES
FOR LOCAL INSTALLATION REQUIREMENTS
Building perimeter wall
Flow
Building Floor
Flow
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
TEST CAP
NOW INCLUDED!
TR
LEAD FREE
*
*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.