User Manual
2
How to order 
Locate the manufacturer and model number under the valve size column in the matrix on these two pages. It is assumed that the 
valve you will be installing is a Watts 774 Sentry Series. On the first line across from the model number is the lay length of the valve 
less gates. On the lines listed below is the valve being replaced. On that line is the lay length of that valve. The column to the right 
is the length of the spool needed to “make up” the difference between the valve being replaced and the lay length of the “Sentry 
Series.” Below the spool length is the ordering code for that spool.
Retrofit Spool Pieces for Various Lengths  •   Cast Iron Watts Products vs Watts Sentry Series 
 WATTS    ACTUAL SPOOL    ACTUAL SPOOL    ACTUAL SPOOL    ACTUAL SPOOL    ACTUAL SPOOL    ACTUAL SPOOL 
 MODEL  2
1
⁄2"†  LENGTH NEEDED  3"†  LENGTH NEEDED  4"†  LENGTH NEEDED  6"†  LENGTH NEEDED  8"†  LENGTH NEEDED  10"†  LENGTH NEEDED
774  22"  - 22"  - 22" -  27
1
⁄2"  - 29
1
⁄2" - 29
1
⁄2" -
 709/LF709  24"  1
7
⁄8" 24"  1
7
⁄8"  34" 11
7
⁄8"  42
1
⁄2" 14
7
⁄8"  52"  22
3
⁄8"  64"  34
3
⁄8"
 774DCDA 22"  - 22"  - 22" -  27
1
⁄2"  - 29
1
⁄2" - 29
1
⁄2" -
 709DCDA  -  -  24"  1
7
⁄8"  34" 11
7
⁄8"  41
1
⁄2" 13
7
⁄8"  52"  22
3
⁄8"  64"  34
3
⁄8" 
 994  22"  - 22"  - 22" -  27
1
⁄2"  - 29
1
⁄2" - 29
1
⁄2" -
 909/LF909  26
1
⁄8"  4" 26
1
⁄8"  4"  37" 14
7
⁄8"  44
1
⁄2" 16
7
⁄8"  55
1
⁄4" 25
5
⁄8"  67
3
⁄8" 37
3
⁄4" 
 994RPDA 22"  - 22"  - 22" -  27
1
⁄2" - - - - -
 909RPDA  26
1
⁄8"  4" 26
1
⁄8"  4"  37" 14
7
⁄8"  44
1
⁄2" 16
7
⁄8"  55
1
⁄4" - 67
3
⁄8" -
†Size and length of valve being replaced.
For Example: when replacing a Watts 4" 709 with a Watts 4" 774 you would need a spool that is 11
7
⁄8" long. 
The slight decrease in the spools length is to accommodate the flange gasket, approximately 
1
⁄8".
Spool Length from chart: 11
7
⁄8" Subtract Lengths: 12" Ordering code: 0107020
Example:
  WATTS MODEL: 709  WATTS MODEL: 774
  Line Size  Lay Length:  Line Size  Lay Length:
  4"  34"  4"  22"