Autotrol® Performa™ Valve With 400 Series Control Water Conditioning Control System Dealer Installation, Operation and Maintenance Manual
Table of Contents Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Location Selection Water Line Connection Drain Line Connection Brine Line Overflow Line Connection Placing Conditioner into Operation . . . . . . . . . . . . . 5 Electrical Connection 400 Series Control Settings . . . . . . . . . . . . . . . . . . . 6 440i Programming 460i Programming Time of Day Setting Hardness Setting Capacity Setting Calendar Override Setting Common Features . . . . . . . . . . . . . . .
Installation All plumbing and electrical connections must conform to local codes. Not in Bypass Out In In Bypass Out In Inspect unit carefully for carrier shortage or shipping damage. PA S S Water Conditioner 3. Since salt must be added periodically to the brine tank, the location should be easily accessible. BY PA S S PA S S 2. If it is likely that supplementary water treatment equipment will be required, make certain adequate additional space is available. PA S S BY BY 1.
Overflow Line Connection 4. Where the drain line is elevated but empties into a drain below the level of the control valve, form a 7-inch (18-cm) loop at the far end of the line so that the bottom of the loop is level with the drain line connection. This will provide an adequate siphon trap. In the absence of a safety overflow and in the event of a malfunction, the BRINE TANK OVERFLOW will direct “overflow” to the drain instead of spilling on the floor where it could cause considerable damage.
Placing Conditioner into Operation 5. Place the conditioner into operation. A. With the water supply valve completely open, carefully advance the indicator knob COUNTERCLOCKWISE to the center of the BRINE REFILL position. Hold at this position until water starts to flow through the brine line into the brine tank. Do not run for more than one or two minutes. B. Advance the indicator knob COUNTERCLOCKWISE until it points to the center of the BRINE/SLOW RINSE position. C.
400 Series Control Settings 440i Control 460i Control Day Arrow Water Flow Indicator Skipper Wheel Skipper Pins Hour Time Display PM Indicator Access Door Raised Tab Jumper Indicator Knob Indicator Knob Timer Locking Pin Timer Locking Pin Time Arrow Timer Knob Transformer Plug Receptacle Spare Jumper Time Set Button Figure 6 Figure 5 Programming Programming Plug the wall-mount transformer into a functioning electrical outlet that is not controlled by a switch.
Hardness Setting 4. Depress the black TIME SET button. The numbers will roll from “0” to “15.” Release the switch at the desired number of days for the calendar override. For example, releasing the switch at “10” would program a 10-day calendar override. Move the jumper to the set of pins next to the word HARDNESS (Figure 8). Press the black TIME SET button until the hardness of the incoming water supply is displayed. The hardness range is from 1 to 99 grains per gallon. 5. Disconnect power. 6.
Table 1 – Suggested Salt Dial Settings (Pounds of Salt) For Various Size Softeners Capacity Setting (Kilograins) 0.5 Ft3 0.75 Ft3 1.0 Ft3 1.25 Ft3 1.5 Ft3 1.75 Ft3 2.0 Ft3 2.5 Ft3 12 4.5 — — — — — — — 16 9.0 5.5 — — — — — — 20 — 8.5 6.0 — — — — 24 — 14.0 8.5 7.0 — — — — 30 — — 15.0 11.0 9.0 — — — 32 — — 18.5 12.5 10.0 9.0 — — 35 — — — 16.0 12.0 10.0 9.0 — — 1 17.0 14.0 12.0 — 1 1 17.0 14.0 1 21.
Removing the Valve Assembly for Servicing Indicator Arrow 1. Unplug the power cord. 2. Shut off water supply or put bypass valve(s) into bypass position. 3. Remove cover and with screwdriver, relieve tank pressure by pushing open valve No. 7 (rear flapper) on control as shown (Figure 10). Figure 11 4. Remove the camshaft by carefully pushing the securing tab, located at the rear of the camshaft, away from the camshaft until the tab disengages from the camshaft.
Preventive Maintenance Water Meter Maintenance Note: A water meter is used only with the 460i control. If you are using the 440i control, this section does not pertain to your conditioner. Injector Screen and Injector Inspect and clean brine tank and screen filter on end of brine pickup tube once a year or when sediment appears in the bottom of the brine tank. The metering device used with the 460i demand control may require simple maintenance.
Specifications Inlet 2.5 inch (63 mm) Drain 2.5 inch (63 mm) Outlet 8.74 inch (222mm) 11.59 inch (294 mm) 2.88 inch (73 mm) 1.356 inch (34 mm) 3.37-inch (86 mm) 3.66-inch (93 mm) 5.76 inch (146 mm) 5.82 inch (148 mm) Hydrostatic Test Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 psi (20.69 bar) Working Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure Graphs Injector #1031363 Injector #1031364 "A" in a 268 Valve "B" in a 268 Valve 1.00 0.30 0.20 Total 1.25 0.25 0.75 0.20 Rinse 0.05 0.00 0.50 Brine Draw 0.15 0.75 GPM 0.10 M3/hr Rinse GPM M3/hr 0.15 Total 1.00 0.10 0.50 0.05 0.25 0.00 0.00 Brine Draw 0.25 0.00 20 40 400 600 60 PSI 80 100 120 20 800 1000 1200 1400 1600 1800 bar 40 400 600 60 1.25 0.20 0.10 0.05 M3/hr Rinse GPM M3/hr 0.25 Total 0.75 0.10 Brine Draw 0.50 0.05 0.25 0.00 0.15 0.
Identification of Control Valving Valve Disc Principle of Operation 7 Backwash Drain Valves 5 Refill Valve 3 Inlet Valve 1 Brine Valve 6 Rinse Drain Valve 4 Outlet Valve 2 Bypass Valve Flow Diagrams 1 Service Position 2 Backwash Position Hard Water Hard Water Soft Water Soft Water Brine Adjustment 1 Brine Adjustment 1 Inlet Inlet 3 3 2 2 5 5 Outlet 4 Outlet 6 Drain Valve No. 1 - Closed 2 - Open 3 - Closed 4 - Open 5 - Closed 6 - Closed 7 - Open Valve No.
4 Purge Position 3 Brining/Slow Rinse Position Hard Water Hard Water Soft Water Soft Water Brine Adjustment 1 Inlet Inlet 3 2 3 2 5 Outlet 4 5 6 Outlet 7 Drain Valve No. 1 - Closed 2 - Open 3 - Open 4 - Closed 5 - Closed 6 - Open 7 - Closed Valve No. 1 - Open 2 - Open 3 - Closed 4 - Closed 5 - Closed 6 - Open 7 - Closed Mineral Tank Brine Tank Hard Water Soft Water Brine Adjustment 1 Inlet 3 2 5 Valve No.
Replacement Parts Performa Valve 2 13 13 4 5 15 14 9 10 1 3 6 7 12 5 6 19 14 8 3 12 8 8 11 15
Parts List Part Code 1 Part No. 1035606 Description Valve Assembly, w/o Flow Controls Qty. Code 1 8 (440i, 460i) 2 3 Camshaft: Description Brine Refill Control (440i and 460i): 1034261 1 to 10 Pounds Salt 1034263 3 to 19 Pounds Salt Qty.
440i Control 460i Control 2 1 1265 Bypass Part B Y PA S S Code B Y PA S S No. Description 1 440i Control (6 day or 7 day) 2 460i Control Qty. 1 1 3 1040930 1265 Bypass 1 * 1000811 Transformer (440i, 460i): 1000907 Transformer Extension Cord 1 * 3 1 15 feet (4.
Troubleshooting IMPORTANT: Service procedures that require the water pressure to be removed from the system are marked with a ! after the possible cause. To remove water pressure from the system, put the bypass valve or three-valve bypass into the bypass position and open the backwash drain valve (the seventh valve back from the control) with a screwdriver. Restore system water pressure when the service work is completed.
440i Control Troubleshooting Problem 1. Control will not regenerate automatically. 2. Control regenerates at wrong time of day. Possible Cause a. Solution Transformer or motor not connected. a. b. Defective timer motor. b. Replace motor. c. Skipper pins not down on timer skipper wheel. c. Depress pins for days regeneration required. Connect power. d. Binding in gear train of timer. d. Replace timer. a. Time set incorrectly. a. Correct time setting according to instructions.
Problem 9. Control will not regenerate automatically or when button is pressed. Possible Cause a. Solution Electric cord unplugged. a. Connect power. b. No electric power at outlet. b. Repair outlet or use working outlet. c. Defective motor. c. Replace timer. d. Broken gear. d. Replace timer. e. Binding in gear train. e. Replace timer. f. Defective switch. f. Replace timer. 10. Control will not regenerate automatically but will regenerate when button is pressed. a.
Disinfection of Water Conditioners 2. Brine tank conditioners The materials of construction of the modern water conditioner will not support bacterial growth, nor will these materials contaminate a water supply. However, the normal conditions existing during shipping, storage and installation indicate the advisability of disinfecting a conditioner after installation, before the conditioner is used to treat potable water.
© Copyright 2001 Osmonics Printed in USA P/N 1222945 Rev.