User Manual

Flow Rate - Gallons per minute (Water)
Pressure Drop (p.s.i.)
Angle
Globe
2 4 6 8 10 20 40 60 80 100 200 500 1000 2000 5000 10000 20000
100,000
100
80
60
40
30
20
10
8
6
4
3
2
Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C
V
factor of a valve is the flow rate in US GPM at 60° F that will cause a 1 psi drop in pressure.
The factors stated are based upon a fully open valve.
C
V
factor can be used in the following equations to determine Flow (Q) and Pressure Drop (r P):
Q (Flow) = C
V
r P rP (Pressure Drop) = (Q/C
V
)
2
Flow Data
Valve Size - Inches 3 4 6 8 10 12 16 18 20 24
Maximum Continuous
Flow Rate Gpm (Water)
210 485 800 1850 3100 5000 7000 11100 11100 11100
Maximum Intermittent
Flow Rate Gpm (Water)
265 590 1000 2300 4000 6250 8900 14100 14100 14100
CV Factor GPM (Globe) 60 133 224 489 932 1428 2067 2881 2881 2881
CV Factor GPM (Angle) 132 237 534
Estimated
Valve Cover Chamber Capacity
Valve Size (in) 3 4 6 8 10 12 16 18 20 24
fl.oz. 4 10 22 70
U.S. Gal 1-1/4 2-1/2 4 9-1/2 9-1/2 9-1/2
Valve Travel
Valve Size (in) 3 4 6 8 10 12 16 18 20 24
(in) 1/2 3/4 1 1-1/2 2 2-1/2 3 4 4 4
Flow Data - ACV M6500 (Globe) / M61500 (Angle)
3
4
6
8
10
12
16
18 / 20 / 24
4
6
8
Valve Cover Chamber Capacity
Valve Travel
Headloss