User Manual

R
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com
STANDARD COMPONENTS OPTIONS and ACCESSORIES
01/05
Mustang Series
ONE-WAY FLOW ALTITUDE VALVE
with PRESSURE SUSTAINING
FEATURE
Designed for Tank Fill applications
Opens when Tank head pressure is below setpoint
Closes when Tank head pressure is above setpoint
Throttles to maintain minimum upstream pressure
Tank Sense Line is field installed (to Tank or
standpipe)
Adjustable Opening and Closing Speed
Altitude and Sustaining setpoints are adjustable
1 - Main Valve (Single Chamber)
2 - Fig. 22 Accelerator Control
3 - Altitude Control
4 - Check Valve
5 - Pressure Sustaining Control
6 - Adjustable Closing Speed
P - Position Indicator
° X - Isolation Cocks
° FC - Flo-Clean Strainer
° Y - Y-Strainer (Replaces Flo-Clean)
° AOS - Adjustable Opening Speed
° L - Limit Switch
P(L)
1
X
X
5
4
6
2
3
X
Y/FC
CLOSES VALVE
OPENS VALVE
FLOW
(Tank Sense Line)
M127-8 or M6127-8 (Globe)
M1127-8 or M61127-8 (Angle)
m127-8 link