Dimensions - Weight
CWS200H SERIES
OVERALL OVERALL OVERALL
mOdEL TANK IN OUT HEIGHT dEPTH WIdTH BRINE TANK
M4548WH 18"X65" 72.2" 75.8" 78.5" 22.4" 18.1" 24"X41"
M4552WH 21"X62" 72.1" 75.7" 78.3" 22.9" 21.1" 24"X41"
M4558WH 24"X72" 79.2" 82.8" 85.5" 24.3" 24.1" 30"X50"
M4559WH 30"X72" 79.2" 82.8" 85.5" 30.1" 30.1" 39"X48"
M4560WH 36"X72" 87.5" 91.1" 93.8" 36.1" 36.1" 39"X48"
Feed Water Guidelines
pH ...................... 6 to 10
Hardness (maximum) ........ Depends on customers acceptable
hardness leakage level.
Water Pressure ............ 25psi to 125psi (171 kPa to 8.5 bar)
Temperature .............. 34 - 110°F (1 - 43°C)
Free Chlorine (maximum) ..... 1mg/L
Iron (maximum) ............ 1mg/L
Oil and H2S ............... None Allowed
Turbidity ................. Less than 5.0 NTU
For all other guideline information please contact your Watts
representative.
Specifications
ES-WQ-CWS200H 1306 © 2013 Watts
USA: Tel. (800) 659-8400 • www.watts.com
Canada: Tel. (888) 208-8927 • www.watts.ca
A Watts Water Technologies Company
Note: Do not use with water that is microbiologically unsafe or of
unknown quality without adequate disinfection before or after the
system.
Note: This information is not intended to replace the product installation and safety information available or the experience of a trained prod-
uct installer. Please refer to the product installation and safety instructions for further information.
Ordering Information
mOdEL dESCRIPTION SPACE REQUIREd WEIGHT
LBS KGS
M4548WH A0150FM200WH with integral turbine meter 24 x 48 x 89 400 181
M4552WH A0210FM200WH with integral turbine meter 24 x 52 x 89 600 272
M4558WH A0300FM200WH with integral turbine meter 30 x 60 x 96 710 322
M4559WH A0450FM200WH with integral turbine meter 39 x 75 x 106 1160 526
M4560WH A0600FM200WH with integral turbine meter 39 x 81 x 107 1560 707
mINERAL TANK BRINE TANK SOfTENING LBS. SALT PER fLOW RATE & PRESSURE
TANK RESIN GRAVEL TANK SALT CAPACITY REGENERATION SERV dROP BKW
mOdEL SIZE ft
3
SIZE fILL mAx mIN mAx mIN GPm PSI GPm
M4548WH 18x65 5 100 lbs. 24x41 600 150 K 100 K 75 30 54/70 15/25 10
M4552WH 21x62 7 100 lbs. 24x50 600 210 K 140 K 105 42 68/88 15/25 13
M4558WH 24x72 10 200 lbs. 30x50 1200 300 K 200 K 150 60 75/97 15/25 15
M4559WH 30x72 15 400 lbs. 39x48 2200 450 K 300 K 225 90 88/113 15/25 25
M4560WH 36x72 20 500 lbs. 39x48 2200 600 K 400 K 300 120 97/126 15/25 35
Note: Capacities are based on resin manufacturer’s data and are dependent upon influent water TDS, temperature, bed depth, and
flow rates. Feed water must be free of oil and color. Pipe size, tank size, and space requirements are in inches. Capacities and flow rates
expressed above are per tank. Flow rates listed at 25psi drops are for intermittent peak flow rates and are not to be used as continuous flows.
Note: Flow rates listed above are based on pressure drop only. Selecting a system based on pressure drop alone does not guarantee that
the system will proved adequately softened water. System selection should be based on resin quantity, capacity required, feed water analy-
sis, and application requirements.