Install Instructions
Now available, WattsBox Insulated Enclosures,
for more information, send for ES-WB or ES-WB-T.
FIBERGLASS WattsBox
Min. 12"
ASSE approved for vertical installation 
3
⁄4" – 2" fl ow up and down
3
For indoor installations, it is important that the 
valve be easily accessible to facilitate testing and 
servicing. Series 909 may be installed either vertically 
or horizontally. If it is located in a line close to wall, 
be sure the test cocks are easily accessible. A drain 
line and air gap should be piped from the relief valve 
connection as shown, where evidence of discharge 
will be clearly visible and so that water damage 
will not occur. Therefore, never install in concealed 
locations.
Note: Test cock must be located on the  rst or inlet 
shutoff valve.
Flow
Relief Valve 
Below First 
Check Valve
Air In
Water
Out
Main
▼
Min.
4
1
⁄2"
▼
▼
Air* 
Gap
First
Check 
Valve
909QT-S
Vertical Installation - Upward Flow
*For Air Gap information contact your technical   
  sales representative or refer to ES-AG/EL.
In an area where freezing conditions do not occur, Series 909 
can be installed outside of a building. The most satisfactory 
installation is above ground and should be installed in this 
manner whenever possible.
In an area where freezing conditions can occur, Series 909 
should be installed above ground in an insulated enclosure. 
Series 909 may be installed in a vertical or horizontal line and 
in an accessible location to facilitate testing and servicing. A 
discharge line should be piped from the air gap at the relief 
valve connection making sure there is adequate drainage. 
Never pipe the discharge line directly into a drainage ditch, 
sewer or sump. Series 909 should never be installed where any 
part of the unit could become submerged in standing water. 
Consideration should be given to the installation of external 
support structure as applicable.
It is generally recommended that back ow preventers never 
be placed in pits unless absolutely necessary, and then only, 
when approved by local codes. In such cases, a modi ed pit 
installation is preferred.
Two or more smaller size valves can be piped in parallel (when 
approved) to serve a larger supply pipe main. This type of 
installation is employed where increased capacity is needed 
beyond that provided by a single valve and permits testing 
or servicing of an individual valve without shutting down the 
complete line.
The number of valves used in parallel should be determined by 
the engineer’s judgement based on the operating conditions of 
a speci c installation.
Table One - Capacity Required for System
 50 gpm  100 gpm  150 gpm  200 gpm  250 gpm  350 gpm
 Two 
3
⁄4"  Two 1"  Two 1
1
⁄4" Two 1
1
⁄2" Two 1
1
⁄2" Two 2"
 Devices Devices  Devices Devices Devices Devices
Table shows total capacity provided with dual valve installations 
of various sizes.
Installation Indoors
Installation - Outside Building Above Ground
Installation - Parallel Consult Local Codes for Approval
909QT-S
909QT-S
Air Gap
(Drawings not to scale)
RP-IS-909S.indd   3 9/29/08   1:01:06 PM








