Installation Instructions

ENGLISH INSTRUCTIONS
IS-MMV-M1
Series LFMMV
Thermostatic Tempering Valves
Válvulas de mezclado termostáticas
Vannes thermostatiques
1
2",
3
4", 1"
Troubleshooting
IS-MMV-M1 1639 EDP# 1915906 © 2016 WattsIS-MMV-M1 1639 EDP# 1915906 © 2016 Watts
IS-MMV-M1 1639 EDP# 1915906 © 2016 Watts
WARNING: This product contains chemicals known to the
State of California to cause cancer and birth defects or other
reproductive harm.
For more information: Watts.com/prop65
ADVERTENCIA: Este producto contiene sustancias químicas
que en el Estado de California se conocen como causantes
de cáncer y malformaciones u otros daños reproductivos.
Para más información: Watts.com/prop65
AVERTISSEMENT : Ce produit contient des produits chi-
miques reconnus par l’État de Californie comme étant can-
cérigènes et pouvant provoquer des anomalies congénitales
ou affecter la capacité de reproduction.
Pour plus d'informations : Watts.com/prop65
USA: Tel: (978) 689-6066 • Fax: (978) 975-8350 • Watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects
in material and workmanship under normal usage for a period of one year from the date of original ship-
ment. In the event of such defects within the warranty period, the Company will, at its option, replace
or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY
GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL
OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive
remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing
other property which is damaged if this product does not work properly, other costs resulting from labor
charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water
conditions, chemical, or any other circumstances over which the Company has no control. This warranty
shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance
or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow
the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may
not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights
that vary from State to State. You should consult applicable state laws to determine your rights. SO
FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT
BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL
SHIPMENT.
USA: Tel: (978) 689-6066 • Fax: (978) 975-8350 • Watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com
Garantía limitada: Watts Regulator Co. (en adelante, “la Compañía”) garantiza, por un período de un año a
partir de la fecha de embarque original, que sus productos están libres de defectos en materiales y mano de obra
bajo condiciones de uso normal. En caso de que se encuentren tales defectos dentro del período de garantía, la
Compañía reemplazará o reacondicionará, a su elección, el producto sin costo alguno.
LA GARANTÍA AQUÍ ESTIPULADA SE OTORGA EN FORMA EXPRESA Y ES LA ÚNICA GARANTÍA
OTORGADA POR LA COMPAÑÍA EN RELACIÓN CON EL PRODUCTO. LA COMPAÑÍA NO OTORGA NINGUNA
OTRA GARANTÍA, YA SEA EXPRESA O IMPLÍCITA. LA COMPAÑÍA POR LA PRESENTE RENUNCIA
ESPECÍFICAMENTE A TODAS LAS DEMÁS GARANTÍAS, EXPRESAS O IMPLÍCITAS, INCLUYENDO SIN
LIMITACIÓN, LAS GARANTÍAS IMPLÍCITAS DE APTITUD PARA LA COMERCIALIZACIÓN E IDONEIDAD PARA
UN PROPÓSITO EN PARTICULAR.
La solución descrita en el primer párrafo de esta garantía constituirá la única y exclusiva solución por
incumplimiento de garantía, y la Compañía no se hará responsable por daños accidentales, especiales o
indirectos, incluyendo sin limitación, la pérdida de ganancias o el costo de reparación o reemplazo de otra
propiedad que resulte dañada por el mal funcionamiento de este producto, otros costos resultantes por mano
de obra, retardos, vandalismo, negligencia, obstrucciones ocasionadas por materiales extraños, daños debidos
a condiciones adversas del agua, químicos o cualquier otra circunstancia sobre la cual la Compañía no tenga
control. Esta garantía no tendrá validez en cualquier caso de abuso, uso indebido, aplicación incorrecta,
instalación inadecuada, o mantenimiento adecuado o alteración del producto.
Algunos Estados no permiten limitaciones en la duración de una garantía implícita y algunos Estados no permiten
la exclusión o limitación de daños accidentales o indirectos. Por lo tanto, es posible que las limitaciones
anteriores no sean aplicables en su caso. Esta garantía limitada le da derechos legales específicos; usted
podría tener también otros derechos que varían según el Estado. Usted debe consultar las leyes estatales
aplicables para determinar sus derechos. EN LA MEDIDA EN QUE SEA CONGRUENTE CON LAS LEYES
ESTATALES APLICABLES, CUALQUIER GARANTÍA IMPLÍCITA QUE NO SEA RECHAZADA, INCLUYENDO LAS
GARANTÍAS IMPLÍCITAS DE APTITUD PARA LA COMERCIALIZACIÓN E IDONEIDAD PARA UN PROPÓSITO EN
PARTICULAR, SE LIMITA EN SU DURACIÓN A UN AÑO A PARTIR DE LA FECHA DEL EMBARQUE ORIGINAL.
USA: Tel: (978) 689-6066 • Fax: (978) 975-8350 • Watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com
Garantie limitée : Watts Regulator Co. (la « Société ») garantit que chacun de ses produits est exempt de
vice de matériau et de fabrication dans des conditions normales d’utilisation pour une période d’un an à
compter de la date d’expédition d’origine. Dans l’éventualité où de tels vices se manifesteraient pendant
la période de garantie, la Société, à sa discrétion, remplacera ou reconditionnera le produit sans frais.
LA PRÉSENTE GARANTIE EST EXPRESSE ET REPRÉSENTE LA SEULE GARANTIE OFFERTE PAR
LA SOCIÉTÉ POUR CE PRODUIT. LA SOCIÉTÉ N’OFFRE AUCUNE AUTRE GARANTIE, EXPRESSE OU
TACITE. PAR LA PRÉSENTE, LA SOCIÉTÉ REJETTE SPÉCIFIQUEMENT TOUTE AUTRE GARANTIE,
EXPRESSE OU TACITE, NOTAMMENT TOUTE GARANTIE TACITE DE QUALITÉ MARCHANDE OU
D’ADAPTATION À UN BUT PARTICULIER.
Le recours décrit dans le premier paragraphe de cette garantie constitue le seul recours à toute violation
de la présente garantie. La Société ne saurait être tenue responsable de tout dommage accessoire,
spécial ou indirect, y compris, de façon non limitative : la perte de profits ou le coût afférent à la
réparation ou au remplacement d’autres biens qui seraient endommagés par suite du fonctionnement
incorrect dudit produit ; d’autres coûts résultant de frais de main-d’œuvre, de retards, de vandalisme,
de négligence, d’une obstruction causée par des matériaux étrangers, de dommages causés par une
eau impropre, des produits chimiques ou par tout autre événement échappant au contrôle de la Société.
La présente garantie est déclarée nulle et non avenue en cas d’usage abusif ou incorrect, d’application,
d’installation ou d’entretien incorrects ou de modification du produit.
Certains États n’autorisent pas les limitations de durée d’une garantie tacite ou l’exclusion ou la
limitation des dommages accessoires ou indirects. Les limitations susmentionnées peuvent donc ne pas
s’appliquer à vous. Cette garantie limitée vous donne des droits spécifiques et il se peut que vous ayez
aussi d’autres droits qui varient d’un État à l’autre. Veuillez vous référer aux lois applicables de l’État pour
déterminer vos droits en la matière. DANS LA MESURE PERMISE PAR LA LOI APPLICABLE DE L’ÉTAT,
TOUTES LES GARANTIES TACITES NE POUVANT PAS ÊTRE REJETÉES, Y COMPRIS LES GARANTIES
TACITES DE QUALITÉ MARCHANDE ET D’ADAPTATION À UN BUT PARTICULIER, SONT LIMITÉES
QUANT À LEUR DURÉE À UN AN À COMPTER DE LA DATE D’EXPÉDITION D’ORIGINE.
Installation Instructions • Instrucciones de instalación • Instructions d’installation
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can result in death,
serious personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.
LFMMV-UT-M1
LFMMV-QC-M1
Quick-Connect Installation
1. Mark pipe as shown.
This is pipe insertion depth.
2. Clean pipe end.
To Connect
3. If using PEX tubing, insert
pipe stiffener (provided)
into end of pipe.
PEX tubing only
Pipe Stiffener
Tail Piece
4. Push tubing into tailpiece
up to mark.
5. Insert collet clip.
Mark
Collet clip
1
1
/2 in. (38.1mm)
1
3
/4 in. (44.45mm)
1
7
/8 in. (47.63mm)
3
/4 in.Pipe (19.05mm)
1 in.Pipe (25.4mm)
1
/2 in.Pipe (12.7mm)
Figure 3
Typical ASSE 1017 Application
Devices tested to ASSE 1069 or ASSE 1070
such as Watts Series LFUSG or LFMMV should
be used at fixture to prevent possible injury.
1. Let water flow for at least two minutes to allow
supply temperature to stabilize.
2. Calibrate the mixed water outlet temperature
by placing a thermometer in the mixed water
stream.
3. To adjust the setting of the valve, loosen locking
cap screw with hex wrench, see Figure 3. Cap
must be lifted 1/4" to adjust temperature. To
increase the temperature, turn counterclockwise.
To decrease temperature turn clockwise.
4. Lower handle and tighten screw.
5. Check outlet temperature.
Figure 4
Temperature Adjustment
1. Remove collet clip.
To Disconnect
2. Depress collet.
3. Pull tubing from tailpiece.
Collet depressed
Hotter
3
/32" Hex Wrench
Turn
Colder
Unscrew, lift
cap to adjust
Installation
Valve should be installed and adjusted by a licensed contractor in accordance with local
codes and ordinances. Further, this valve should be installed in a location where it is acces-
sible for cleaning, service or adjustment.
1. Close both the hot and cold water shutoff valves upstream nearest to the intended installation.
2. Bleed the remaining water from the system.
3. Connect the water supply to valve as shown in Figure 1, 2 or 3 depending on application.
Supply piping must be flushed clean before making connections to the valve.
4. Valve can be installed in any position. The inlet hot supply is to be connected to the “H” side
of the valve, the cold supply side to the “C” side and the mixed water outlet to the “M” side.
5. Make sure union nuts are placed over tailpieces prior to soldering threading to pipe or using w/press.
6. For valves with Quick-Connect tailpieces refer to "Quick-Connect Installation" instructions below
To prevent damage to valve from excessive heat during soldering, remove unions and gaskets
from valve body prior to soldering.
7. After soldering, flush piping and install valve using filter washer on hot and cold water inlet and
fiber washer on the mixed water outlet.
8. Start-up: Open cold water supply, then hot water supply. Inspect for leaks.
9.
Adjust temperature to desired setting (see Temperature Adjustment Section). Watts recom-
mends a maximum temperature of 105°F (41°C) for shower and bathing fixtures.
Pressure — Temperature — Flow Rate
Minimum Supply Pressure Static: 30psi (207 kPa)
Inlet Temperatures: hot inlet, 120°F – 180°F (49°C – 82°C),
cold inlet, 39°F – 85°F (4°C – 29°C)
Hot Water Inlet to Outlet Differential Temperature: 5°F (3°C)
Temperature Out: Field range: 80°F – 120°F (27°C – 49°C), adjustable;
Accurate within ±3°F (1.7°C)
Maximum Temperature: 200°F (93°C)
Maximum Pressure: 150psi (1034 kPa)
Minimum Flow: 0.5 gpm (1.9 lpm) @.08psi (0.55 kPa)
Maximum Flow: 20 gpm (76 lpm) @ 125psi (862 kPa)
Maximum Pressure Differential between
Hot & Cold Water Supplies: 25% maximum differential
Listing: ASSE 1017, ASSE 1069, ASSE 1070 and IAPMO cUPC
When tested in accordance with ASSE 1017, ASSE 1069, ASSE 1070
and IAPMO cUPC
NOTICE
NOTICE
Viega Pro-Press
connections
are optional factory installed
fitting on each end of the
approved/certified assembly
WARNING
!
For valves with CPVC or PEX end connections, do not exceed the tubing manufacturers pressure and
temperature ratings. Refer to the tubing manufacturers product specifications for that information.
Triple Listed!
ASSE 1017,
ASSE 1069 & ASSE 1070
FAILURE TO COMPLY WITH PROPER INSTALLATION AND MAINTENANCE
INSTRUCTIONS COULD CONTRIBUTE TO THE VALVE FAILURE, RESULTING IN
INJURY AND/OR DEATH.
TO ENSURE THE ACCURATE AND RELIABLE OPERATION OF THIS PRODUCT,
IT IS ESSENTIAL TO:
Properly design the system to minimize pressure and temperature variations.
This valve is not factory preset and can be adjusted to deliver scalding tempera-
tures. Check outlet temperature to ensure it does not exceed 105°F (41°C).
Make sure temperature limit stop is properly re-set to maximum 105°F (41°C) fol-
lowing valve maintenance or repair. Tampering with limit stop in any way may result
in scalding temperature causing serious bodily harm and/or death.
WARNING
!
WARNING
!
Need for Periodic Inspection and Yearly Maintenance:
Periodic inspection and yearly maintenance by a licensed contractor is required.
Corrosive water conditions and/or unauthorized adjustments or repair could ren-
der the valve ineffective for service intended. Regular checking and cleaning of
the valve’s internal components and check stops helps assure maximum life and
proper product function. Frequency of cleaning and inspection depends upon
local water conditions.
You are required to consult the local building and plumbing codes prior to installation.
If the information in this manual is not consistent with local building or plumbing codes,
the local codes should be followed. Inquire with governing authorities for additional
local requirements.
WARNING
!
*The wetted surface of this product contacted by consumable water contains less than
0.25% of lead by weight.
Cold
Watts
Vacuum Relief
Valve
Watts
Temperature
Gauge
Cold
Cold
Tempered
Hot
Hot to
Appliances
Watts T&P
Relief Valve
*8" – 12"
H
C
M
LFMMV-M1
It is recommended that shutoff valve(s)
be installed on the inlet(s) to facilitate
service of the LFMMV-M1 valve.
Figure 1
Typical ASSE 1069 Application
Hot
140°F
Cold
Cold
LFMMV-M1
Mixed
110°F
Mixed
110°F
Hot
Cold
Cold
Supply
Stops
Typical
Two Handled Faucet
Typical
Two Handled Faucet
Typical LFMMV-M1 Applications
Cold
Hot
LFMMV-M1
Mixed
Figure 2
Typical ASSE 1070 Application
NOTICE
To prolong the life of the series LFMMV
when used in an ASSE 1017 application,
it is recommended that it be trapped
as shown; i.e. the hot water inlet to the
LFMMV should be 8"-12" (200-305mm)
below the hot water supply feed.
Problem & Cause
A. Unable to reach required set point or set point difficult to set
A.1 Supply temperatures not within specified limits
A.2 Hot and cold supplies reversed
A.3 Filters are blocked by debris
B. Unable to achieve required flow
B.1 Too much pressure drop at fixture
B.2 Checks valve/filters blocked by debris
C. Valve does not maintain required temperature or tempera-
ture changes over time
C.1 Fluctuation in supply pressures
C.2 Check valve/filters blocked by debris
C.3 Recirculation loop not piped properly
D. Discharge temperature too hot or cold
D.1 Valve not calibrated properly
E. Hot water from cold water tap or cold from hot
E.1 Check valves fouled
F. Valve is noisy
F.1 Water velocity is too high
F.2 Valve not sized properly
G. No flow from valve
G.1 Hot or cold water supply failure or shutoffs closed
G.2 Check valve/filters blocked by debris
H. Flow from valve fluctuates
H.1 Fluctuation in supply pressures
H.2 Check valve/filters blocked by debris
Answer
A.1 Check differential temperature between hot and cold supplies
and outlet 5°F (-15°C) minimum required
A.2 Reinstall valve with supplies connected to marked inlets
A.3 Clean filters
B.1 Measure supply pressures and check against flow chart.
Look for restrictions in valve or piping
B.2 Clean check valves/filters
C.1 Stabilize water pressures with pressure regulating or
balancing valves
C.2 Clean check valves/filters
C.3 Pipe recirculated tempered water return so it connects
to hot water source and cold side of Tempering valve
(see Product Guide for piping details)
D.1 Readjust valve temperature per installation instructions
E.1 Clean check valves/filters
F.1 Reduce water velocity with pressure regulating valves
F.2 Check flow required versus rated flow capacity of valve
G.1 Open shutoffs or restore hot and cold supply
G.2 Clean check valves and filters
H.1 Stabilize water pressure with pressure regulating valves
H.2 Clean check valves and filters

Summary of content (2 pages)