Specification Sheet

Size
3
4"
CSA Rated. Standard Models are self-closing T&P Relief Valves for
Water Heaters up to 105,000 BTU/Hr.
Watts Series LFSL100XL, LFL100XL , LFLL100XL and LFLLL100XL
have extended inlet shanks for use with the new generation of water
heaters containing extra thick insulation. These valves eliminate the
use of an extension nipple required with standard shank length mod-
els. They feature Lead Free* construction to comply with Lead Free*
installation requirements.
The combined 2-in-1 Temperature & Pressure relief valve provides the
least expensive and proven means for protection against both exces-
sive temperature and pressure emergency conditions.
Watts Self-closing combination T&P relief valves are design certified,
rated and listed by CSA to the requirements of ANSI Z21.22; and by
the National Board to the requirements of ASME Section IV.
They provide fully automatic temperature and pressure relief protec-
tion for hot water storage tanks and heaters up to 105,000 BTU/Hr.
The temperature sensing element must be immersed in the water
within the top 6" (152mm) of the tank. Male inlet and female outlet.
Temperature relief 210°F (99°C). Standard setting 75, 100, 125,
150psi (5.3, 7.0, 8.8, 10.6 bar).
Features
Model LFSL100XL Extended inlet model for installations with thick
insulation. Suitable for water heaters with up to 1
3
4" (44.5mm)
of insulation
Model LFL100XL Extended inlet model for installations with thick
insulation. Suitable for water heaters with up to 2" (50.8mm)
of insulation
Model LFLL100XL Extra extended inlet model. Suitable for water
heaters with up to 2
1
2" (63.5mm) of insulation
Model LFLLL100XL Extra extended inlet model. Suitable for water
heaters with up to 3" (76mm) of insulation
Thermostats with special protective coating
All Lead Free* brass body
Stainless steel spring
Thermostat is accurate and proven. Exclusively designed and
manufactured by Watts
LFLLL100XL
LFLL100XL
LFL100XL
LFSL100XL
Series LFSL100XL,
LFL100XL, LFLL100XL
and LFLLL100XL
Extended Shank T&P Relief Valves
Following installation, the valve lever MUST be operated AT
LEAST ONCE A YEAR to insure that the waterways are clear.
Certain naturally occurring mineral deposits may adhere to the valve,
rendering it inoperative. When manually operating the lever, please take
precautions to avoid contact with hot water that may discharge and to
avoid water damage. BEFORE operating lever, check to see that a
discharge line is connected to this valve directing the flow of hot water
from the valve to a proper place of disposal, otherwise personal injury
may result. If no water flows, valve is inoperative. TURN OFF THE
WATER HEATER AND CALL A PLUMBER IMMEDIATELY.
This device is designed for emergency safety relief and shall not be
used as an operating control.
Specifications
Temperature & Pressure Relief Valves
Each hot water storage heater shall be equipped with a CSA and
ASME rated automatic temperature and pressure relief valve to pro-
tect the heater from excessive pressure and excessive temperature.
The device shall be design certified, rated and listed by CSA to the
requirements of ANSI Z21.22; and by the National Board to the
requirements of ASME Section IV. The BTU discharge capacity of
the device shall be in excess of the BTU input rating of the heater.
The Lead Free* Extended Shank T&P Relief Valves shall comply with
state codes and standards, where applicable, requiring reduced
lead content. Watts Series LFSL100XL, LFL100XL, LFLL100XL or
LFLLL100XL.
WARNING
!
For Water Heater Applications
ES-LFSL-100XL/LFL100XL/LFLL100XL/LFLLL100XL
LEAD FREE
*
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.
NOTICE
Inquire with governing authorities for local installation requirements
The information contained herein is not intended to replace the full
product installation and safety information available or the experience
of a trained product installer. You are required to thoroughly read all
installation instructions and product safety information before begin-
ning the installation of this product.
NOTICE