Install Instructions
7
  Symptom  Cause  Solution
  1. Check valve fails to hold  a. Debris on check disc  Disassemble and clean
    1.0 PSID minimum    sealing surface   
      b. Leaking gate valve  Disassemble and clean or repair
      c. Damaged seat disc or  Disassemble and replace
        seat o-ring 
      d. Damaged guide holding  Disassemble clean or replace
        check open 
      e. Weak or broken spring  Disassemble and replace spring
  2. Chatter during flow  a. Worn, damaged or  Disassemble and repair or
    conditions    defective guide  replace guide
  3. Low flows passing  a. Mainline check fouled  Disassemble and clean
    through mainline     
    valve (709DCDA only)     
      b. Meter strainer plugged  Disassemble and clean
      c. Damaged mainline seat  Disassemble and replace
        disc or seat 
      d. Broken mainline spring  Disassemble and replace
Troubleshooting Guide