User Guide

IS-TK-9A
Watts TK-9A
Backflow Preventer Test Kit
The Watts No. TK-9 Model “A” Backflow Preventer Test Kit is a
compact portable testing device made for testing all Reduced
Pressure Zone Backflow Prevention Assemblies and Double
Check Valve Assemblies. The TK-9A is easily connected to any
RPZ device enabling accurate testing of zone differential
pressure, relief valve opening differential, fouled check valves
or similar problems that visual inspections cannot locate. The
unit is supplied with a rugged carrying case for easy handling
and accessibility.
Specifications
Maximum working pressure – 175 psi (12.1 bar).
Maximum working temperature – 210°F (99°C).
Gauge - 4
1
2" diameter face dual scale 0 – 15 psid and
0-1 kg/cm2, ±2% accuracy full scale.
Test Valves – (2) ball valves and (1) needle valve.
Hoses – (3) 3’ with female threaded swivel couplings.
Adaptors – (3)
1
4" threaded coupling adaptors
(3)
1
2" x
1
4" bushings
(3)
3
4" x
1
4" bushings
1 – 16" securing strap.
1 – Moisture resistant instruction guide.
Case – light weight, shock resistant molded plastic with
foam inserts.
For digital printout model test kit, request F-TK-DL.

Summary of content (4 pages)