Specification Sheet
The combined 2-in-1 Temperature & Pressure Relief Valve provides
the least expensive and proven means for protection against both
excessive temperature and pressure emergency conditions.
Fully automatic temperature and pressure relief protection for domes-
tic hot water supply tanks and heaters based on the latest ANSI
Z21.22 Listing requirements for temperature discharge capacity.
40XL with test lever and extension thermostat for installation in
hot water outlet within the allowable distance from the top of the
tank based on latest ANSI Z21.22. Sizes
3
⁄4" and 1".
40L with test lever and short thermostat for installation directly in
available tank tappings. Sizes
3
⁄4" and 1".
Series 140, N240 and 340 have the same basic body construction
and advanced design features as the Series 40 and are identical
to the Series 40 except for discharge capacity and size of inlet and
outlet connections. For complete specifications (including specifica-
tions for the Series 40) see other side. Sizes 1", 1
1
⁄4", 1
1
⁄2" and 2".
Features
• Bronze body construction
• Non-mechanical seat-to-disc alignment
• Thermostat is accurate and proven. Exclusively designed and
manufactured by Watts
• Tamper-resistant bonnet screws
• Series 40 and 140 feature a unique thermostat with a special
thermo-bonded coating
• Series 140 sizes 1" and above are standardly furnished with
stainless steel thermostat tube
• Series N240, 340 and 342 are furnished with stainless
steel thermostat
Specifications
Temperature & Pressure Relief Valves
Each hot water storage heater shall be equipped with an auto-
matic temperature and pressure relief valve to protect the heater
from excessive pressure and excessive temperature. The device
shall be certified as meeting the requirements of ASME low pres-
sure heating boiler code and ANSI Z21.22. The BTU discharge
capacity of the device shall be in excess of the BTU input rat-
ing of the heater. The T&P valve shall be a Watts Series 40, 140,
240 or 340.
Standards
ASME Rated, ANSI Z21.22, Design certified and listed by CSA,
National Board of B&PVI to Section IV of the ASME B&PV code
and meet current FHA requirements and ANSI Z21.22 in addition
to Military Spec. MIL-V-136-12D, Type I.
Pressure – Temperature
Temperature Relief: 210°F (99°C)
Pressure Range: 75 – 150psi (5.2 – 10.3 bar)
Standard Setting: 75, 100, 125 and 150psi
(5.2, 6.9, 8.6 and 10.3 bar)
Series 40L and 40XL
Series 140XL
Series N240X
Series 340
Series 40, 140, 240 & 340
Automatic Re-seating T&P Relief Valves
NOTICE
Inquire with governing authorities for local installation requirements
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
For Commercial Water Heater Applications
ES-40-140-240-340
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
Following installation, the valve lever MUST be operated
AT LEAST ONCE A YEAR to ensure that the water-ways are
clear. Certain naturally occurring mineral deposits may adhere to
the valve, rendering it inoperative. When manually operating the
lever, water will discharge and precautions must be taken to avoid
contact with hot water and to avoid water damage. BEFORE
operating lever, check to see that a discharge line is connected
to this valve directing the flow of hot water from the valve to a
proper place of disposal otherwise personal injury may result. If
no water flows, valve is inoperative. TURN OFF THE WATER
HEATER AND CALL A PLUMBER IMMEDIATELY.
This device is designed for emergency safety relief and shall not
be used as an operating control.
WARNING
!
The information contained herein is not intended to replace the full
product installation and safety information available or the experience
of a trained product installer. You are required to thoroughly read all
installation instructions and product safety information before begin-
ning the installation of this product.
NOTICE