Install Instructions

Installation Instructions
Model 53 Pressure Relief Valves
For pressure relief only. Furnished without a lever.
1
2" female drain. Pressure range
75-175psi (5.17-12.06 bar). Setting 50, 75, 125 and 150psi (3.45, 5.17, 8.61 and 10.34 bar).
Series 530C and LF530C Calibrated Pressure Relief Valves
Calibrated adjustment allows for setting valve to required pressure relief. Adjustable range
50-175psi (3.45-12.06 bar). The Series 530C is ideal for bypass thermal expansion pressure
relief. This valve is not an ASME approved safety relief valve and should not be used in sys-
tem applications with this requirement.
Series 30L Pressure Relief Valves
For pressure relief only. Pressure range 75 to 150psi (5.17-10.34 bar). Not diaphragm actu-
ated. Std. setting 100, 125 and 150psi (6.90, 8.61 and 10.34 bar).
30L-Z1 -
1
2" 75psi (5.17 bar) - Well system relief valve. Capacity: 20 gpm at 10psi over pres-
sure (85psi).
111/111L -
1
2" &
3
4" (15 & 20mm) pressure relief valve only. The 111L is furnished with a
lever. Standard setting is 125psi (6.9 bar), max. temperature 180°F (82°C).
IS-53/530/30L/111
Dielectric Unions
Cold
Water
Heater
Reduced
Pressure
50psi
Cold Supply
Water Pressure
Reducing Valve
Hot
Set Tub
Auxiliary Relief
Valve Can Be
Installed On
Either Hot Or
Cold Piping
*T&P valve should be set according to tank working
pressure or local code requirements.
**Only where code approved. NOTE: Resulting sys-
tem pressure will be as high as bleeder valve setting
(usually 125psi).
**Watts Auxiliary
Thermal Expansion
Pressure Relief
Valve
No. 53, Series
530C, 30L or 111
*Watts T&P
Safety Relief
Valve Set At
150psi
One-Way
Flow Device
No. 30L
No. 111
No. 530C
Purpose
Auxiliary (bleeder) pressure relief valve is set
approximately 25psi (172 kPa) lower than
heater T&P valve and eliminates unneces-
sary and frequent relief from hot water
heater T&P relief valve. This protects the
system from thermal expansion pressure
buildup during times when reducing valve
thermal expansion bypass is ineffective due
to high inlet water pressure. The adjustable
Series 530C is preferred to provide a range
of settings adaptable to any installation.
Some national and regional codes require
maximum static (no-ow) pressure at any
xture to be not more than 80psi (5.5 bar).
Location
Install auxiliary (bleeder) pressure relief
valve downstream of the reducing valve,
in any convenient location where slight
spillage is not objectionable. If spillage is
frequent, install to drain in set tubs or other
drain location.
Auxiliary (Bleeder) Pressure Relief Valve for Thermal Expansion Relief
No. 53
IS-53/530/30L/111 0940 EDP# 1910868 © 2009 Watts
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com
Canada: 5435 North Service Rd., Burlington, ONT. L7L 5H7; www.wattscanada.ca
A Watts Water Technologies Company
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of
original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting
from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no
control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above
limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
Model 530C and LF530C Calibrated Pressure
Relief Valve Model 53, 30L and
111 Pressure Relief Valves