Submittal Sheet

For Commercial Water Heater Applications
ES-LFLL/LLL-40XL
LEAD FREE
*
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.
Series LFLL40 and
LFLLL40
Extended Inlet Shank Automatic
Re-seating T&P Relief Valves
Sizes:
3
4" and 1"
The combined 2-in-1 Temperature & Pressure relief valve provides
the least expensive and proven means for protection against both
excessive temperature and pressure emergency conditions.
Full automatic temperature and pressure relief protection for com-
mercial hot water supply tanks and heaters based on the latest ANSI
Z21.22 listing requirements for temperature discharge capacity.
LFLL40XL and LFLLL40XL with test lever and extended inlet shank
for use with the new generation of water heaters with extra thick
insulation. These valves eliminate the use of an extension nipple
required with standard shank length models.
Watts self-closing combination T&P relief valves are design certified
and listed by CSA and NB.
Features
Lead Free* cast copper silicon alloy
Non-mechanical seat-to-disc alignment
Thermostat is accurate and proven. Exclusively designed and
manufactured by Watts
Tamper-resistant bonnet screws
Unique thermostat with a special thermo-bonded coating
Specifications
Temperature & Pressure Relief Valves
Each hot water storage heater shall be equipped with an automatic
temperature and pressure relief valve to protect the heater from
excessive pressure and excessive temperature. The device shall be
certified as meeting the requirements of ASME low pressure heating
boiler code and ANSI Z21.22. The BTU discharge capacity of the
device shall be in excess of the BTU input rating of the heater. The
device shall be constructed using Lead Free* cast copper silicon
alloy material. Lead Free* automatic re-setting T&P relief valve shall
comply with states codes and standards, where applicable requiring
reduced lead content. Valve shall be a Watts Series LF40.
3
4" LFLL40XL
1" LFLL40XL
3
4" LFLLL40XL
1
21
32"
3
21
32"
1
25
32"
Standards
ASME rated, ANSI Z21.22. Design certified and listed by CSA. Meets
current FHA and ANSI Z21.22 requirements in addition to Military
Spec. MIL-V 136-12D, Type I.
Pressure - Temperature
Temperature relief 210°F (98.9°C). Pressure range 75-150psi (5.17-
10.34 bar). Standard setting 75, 100, 125 or 150psi (5.17, 6.9, 8.61
and 10.34 bar).
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Following installation, the valve lever MUST be operated
AT LEAST ONCE A YEAR to ensure that the water-ways
are clear. Certain naturally occurring mineral deposits may
adhere to the valve, rendering it inoperative. When manually
operating the lever, water will discharge and precautions
must be taken to avoid contact with hot water and to avoid
water damage. BEFORE operating lever, check to see that
a discharge line is connected to this valve directing the flow
of hot water from the valve to a proper place of disposal
otherwise personal injury may result. If no water flows,
valve is inoperative. TURN OFF THE WATER HEATER
AND CALL A PLUMBER IMMEDIATELY.
WARNING
!
NOTICE
This device is designed for emergency safety relief and shall not
be used as an operating control.
The information contained herein is not intended to replace the full
product installation and safety information available or the experience
of a trained product installer. You are required to thoroughly read all
installation instructions and product safety information before begin-
ning the installation of this product.
NOTICE