Instructions / Assembly
Specification
A Reduced Pressure Zone Assembly shall be installed at each
potential health hazard location to prevent backflow due to back-
siphonage and/or backpressure. The assembly shall consist of an
internal pressure differential relief valve located in a zone between
two positive seating check modules with captured springs and
silicone seat discs. Seats and seat discs shall be replaceable
in both check modules and the relief valve. There shall be no
threads or screws in the waterway exposed to line fluids. Service
of all internal components shall be through a single access
bronze cover secured with stainless steel bolts. The assembly
shall also include two resilient seated isolation valves, four resilient
seated test cocks, and an air gap drain fitting. The assembly shall
meet the requirements of USC; ASSE Std. 1013; AWWA Std.
C511-92; CSA B64.4. Shall be a Watts Series 009.
Available Models
Prefix:
C – Clean and check strainer (
3
⁄4" – 1")
U – Union connections (For more information download
ES-U009-FS at watts.com.)
Suffix:
AQT – Elbow fittings for 360° rotation (
3
⁄4" – 2")
HC – 2
1
⁄2" Inlet/outlet fire hydrant fitting (2")
LF – Without shutoff valves
PC – Internal polymer coating
QT – Quarter-turn ball valves
S – Bronze strainer
SH – Stainless steel ball valve handles
Materials
Bronze body construction, silicone rubber disc material in the
first and second check plus the relief valve. Replaceable poly-
mer check seats for first and second checks.
Removable relief
valve seats. Stainless steel cover bolts.
Standardly furnished with NPT body connections. For optional
bronze union inlet and outlet connections, specify prefix U
(
1
⁄2" – 2"). Series 009QT furnished with quarter turn, full port,
resilient seated, bronze ball valve shutoffs.
Pressure / Temperature
Suitable for supply pressure up to 175 psi (12.1 bar)
Water temperature: 33°F – 180°F (0.5°C – 75°C)
Standards
USC
ASSE No. 1013
AWWA C511-92
CSA B64.4
IAPMO File No. 1563
Approvals
ASSE, AWWA, CSA, IAPMO
Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
UL Classified
3
⁄4" – 2"
(LF models only except 009M3LF)
Insulated Enclosure
The WattsBox insulated enclosure is available for
Series 009/009-FS. For more information download ES-WB at
watts.com.