Instructions / Assembly

ES-009/009-FS
Series 009 and 009-FS
Reduced Pressure Zone Assemblies
Size:
1
4" – 2"
Series 009 and 009-FS Reduced Pressure Zone Assemblies are
designed to protect potable water supplies in accordance with
national plumbing codes and water authority requirements. This
series is designed to protect drinking water supplies from dan-
gerous cross-connections in accordance with national plumbing
codes and water authority requirements for non-potable service
applications such as irrigation, fireline, or industrial processing.
The series features two in-line, independent check valves, captured
springs, and replaceable check seats with an intermediate relief
valve. Its compact modular design facilitates easy maintenance and
assembly access. Sizes
1
4" to 1" shutoffs have tee handles.
Series 009-FS assemblies of sizes ½" to 2" include an integrat-
ed flood sensor to detect excessive water discharges from the
relief valve. When activated through an add-on sensor connec-
tion kit, the flood sensor relays a signal that triggers notification
to qualified service personnel who can take corrective action,
thus avoiding the possibility of ruinous flooding and costly dam-
age. The add-on sensor connection kit is available for both
building management systems, or BMS, and cellular communi-
cation. (For more information, refer to Installation, Maintenance,
and Repair Manual, Series 009-FS and LF009-FS.)
Features
Single access cover and modular check construction
for ease of maintenance
Top entry to all internals for immediate accessibility
Captured springs for safe maintenance
Internal relief valve for reduced installation clearances
Replaceable seats for economical repair
Bronze body construction for durability (
1
4" – 2")
Ball valve test cocks — screwdriver slotted (
1
4" – 2")
Large body passages provides low pressure drop
Compact, space saving design
No special tools required for servicing
Integrated sensor for flood detection (
1
2" – 2")
Test Cock No. 3
Test Cock No. 4
R.P. Zone
Water Outlet
Test Cock
No. 2
First Check
Module
Assembly
Second
Check
Module
Assembly
Relief Valve Assembly
Ball Type
Test Cocks
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
NOTICE
Inquire with governing authorities for local installation
requirements.
The information contained herein is not intended to replace the
full product installation and safety information available or the
experience of a trained product installer. You are required to
thoroughly read all installation instructions and product safety
information before beginning the installation of this product.
NOTICE
Engineering Specification
It is illegal to use this product in any plumbing system providing
water for human consumption, such as drinking or dishwashing,
in the United States. Before installing standard material product,
consult your local water authority, building and plumbing codes.
WARNING
!