Using EZware-5000    67 
Action modes include Bit ON, Bit OFF, or Word write. 
Bit ON: Start action sets the Action address bit. End action clears the Action address bit. 
Bit OFF: Start action clears the Action address bit. End action sets the Action address bit. 
Word write value settings – Constant: Start action writes the Start value into the Action address register. End action 
writes the End value into the Action address register. 
Word write value settings – Address: Start action writes the value stored in the designated register into the Action 
address register. End action writes the value stored in the designated register+1 into the Action address register. 
Note: The end action is only available when Enable termination action is checked on the Time Set tab. 
Click the Time Set tab to configure the start and end times for the scheduled action. When Constant is selected, the 
action is configured to occur on the specified days at the specified times. Multiple days can be selected. If the start 
and end times need to span several days, select the Setting on individual day checkbox. 
When Address is selected, the start and end times are determined by values in 11 consecutive registers beginning 
with the designated Time setting address as follows: 
Address 
Function 
Details 
Time setting address 
Control 
Set to 1 to load the Scheduler with 
the current time data. Do this each 
time the start and end times are 
updated in the registers. 
Time setting address + 1 
Status 
Bit 0 is set when the time data has 
been properly loaded. 
Bit 1 is set when there has been an 
error in loading the time data. 
Time setting address + 2 
Action mode 
Set Bit 0 to use end time. 
Clear Bit 0 and the Scheduler will not 
use end time. 
Time setting address + 3 
Start time (day) 
Bits 0-6 determine day of the week 
the Start Action is executed. 
Bit 0=Sunday; Bit 6=Saturday. 
Time setting address + 4 
Start time (hour) 
This register determines the hour the 
Start Action is executed. 
Range is 0-23. 
Time setting address + 5 
Start time (minute) 
This register determines the minute 
the Start Action is executed. 
Range is 0-59. 
Time setting address + 6 
Start time (second) 
This register determines the second 
the Start Action is executed. 
Range is 0-59. 
Time setting address + 7 
End time (day) 
Bits 0-6 determine day of the week 
the End Action is executed. 
Bit 0=Sunday; Bit 6=Saturday. 
Note: If bit 0 of the Action Mode 
register is clear, the Scheduler will 
not execute the End Time action. 