Manual
26    EZware5000 Series Programming Manual 
Troubleshooting 
The HMI must be connected to a PLC/controller in order for the project to run correctly in the HMI. If there is a 
problem with communications between the HMI and PLC/controller, the “PLC no response” message (window 5) will 
appear on the screen and objects addressing PLC registers will not appear on the screen. Here are some things to 
check if this occurs: 
1.  Make sure you have selected the correct communication protocol (driver) for the PLC you are using in the 
System Parameters (Edit > System Parameters > Device Properties). 
 The demo version of EasyBuilder-5000 will not download the driver to the HMI and will automatically 
generate a “PLC no response” error message. 
2.  Make sure the communication settings in the HMI (Edit > System Parameters > Device Properties) match the 
communication settings in the PLC. 
3.  Make sure the communication cable is wired correctly for your application. Refer to the Controller Cable 
Assembly drawings on our website for specific cabling information for your PLC/controller. 
(http://www.maplesystems.com/cables1023.htm
). 
4.  Check the address formatting for objects that are reading from or writing to registers in the PLC. If the 
objects cannot access specific registers in the PLC, they will not appear on the screen. Refer to the Controller 
Information Sheet for your particular PLC/controller for specific information about accessible registers in the 
PLC memory and the correct addressing format for the various registers. 
(http://www.maplesystems.com/products/prodbycon-bot.htm
) 