178    EZware5000 Series Programming Manual 
In order for a user to login, they must first enter their user number into reserved local word LW9219. Then they must 
enter their password into reserved local word LW9220 (32-bit unsigned). 
 This procedure is different from what was used in EasyBuilder-500, where the user only needed to enter a 
password. 
There are several other reserved local words and bits that can add functionality to your security implementation. 
Reserved Local Memory 
Function 
LW9222 
Displays the access levels assigned to the currently logged-in user 
in binary format (16-bit binary) 
Bit 0: A, Bit 1: B, Bit 2: C, Bit 3: D, Bit 4: E, Bit 5: F 
LW9500-LW9523 (32-bit unsigned) 
Stores user passwords 1-12 
LB9050 
Logs out user and resets password to zero when bit is set (HMI 
resets bit to zero) 
LB9060 
Indicates when an invalid password has been entered (bit resets 
to zero when valid password is entered) 
LB9061 
Set to update user passwords when changed locally  
(LW9500-LW9523) Use momentary style 
Refer to the Security Sample Project on our website to see how to employ the above reserved local memory bits and 
registers in a security implementation. 
(http://www.maplesystems.com
 > Support Center > Sample Projects > HMI5000 Series > Sample Prj: Security) 
1010-1007, Rev. 10 