User guide

Watlow Series SD Limit 30 Chapter 6 Operations
Note: Parameters appear in the Operations Page only if activated from the Programming Page.
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Operations Parameters Table
6
These parameters can be selected to appear in the Operations Page. Select parameters to appear in the Operations
Page in the Programming Page.
Press the Advance Key from the Home Page to enter the Operations Page. To return to the Home Page, press
the RESET Key.
[L1;Lo]
[L1.Lo]
Limit 1 Low
Set the low limit set point value for Out-
put 1.
[SP;Lo] to [SP;hi]
74
*102, 103
R/W
[LSd1] is set to
[both] or [Low].
[L1;hi]
[L1.hi]
Limit 1 High
Set the high limit set point value for
Output 1.
[SP;Lo] to [SP;hi]
75
*104, 105
R/W
[LSd1] is set to
[both] or [high].
[L2;Lo]
[L2.Lo]
Limit 2 Low
Set the low limit set point value for Out-
put 2.
[SP;Lo] to [SP;hi]
74
*117, 118
R/W
If [Ot~2] is set to
[LIM] and [LSd2] is
set to [both] or
[Low].
[L2;hi]
[L2.Lo]
Limit 2 High
Set the low limit set point value for Out-
put 2.
[SP;Lo] to [SP;hi]
75
*119, 120
R/W
If [Ot~2] is set to
[LIM] and [LSd2] is
set to [both] or
[high].
[A2;lo]
[A2.Lo]
Alarm 2 Low
Set the low alarm set point for Output
2.
Process: range of sensor, if
[`SEN] is set to [``tc] or
[`rtd]
-1999 to 9999 if [`SEN] is
set to [`Ma], [uolt], or
[`Mu].
(-1999000 to 9999000)
32
*117, 118
R/W
If [Ot~2] is set to
[Pr;AL]
[A2;hi]
[A2.hi]
Alarm 2 High
Set the high alarm set point for Output
2.
Process: range of sensor, if
[`SEN] is set to [``tc] or
[`rtd]
-1999 to 9999 if [`SEN] is
set to [`Ma], [uolt], or
[`Mu].
(-1999000 to 9999000)
1500
*119, 120
R/W
If [Ot~2] is set to
[Pr;AL]
[L3;Lo]
[L3.Lo]
Limit 3 Low
Set the low limit set point value for Out-
put 3.
[SP;Lo] to [SP;hi]
74
*132, 133
R/W
If [Ot~3] is set to
[LIM] and [LSd3] is
set to [both] or
[Low].
[L3;hi]
[L3.Lo]
Limit 3 High
Set the low limit set point value for Out-
put 3.
[SP;Lo] to [SP;hi]
75
*134, 135
R/W
If [Ot~3] is set to
[LIM] and [LSd3] is
set to [both] or
[high].
[A3;lo]
[A3.Lo]
Alarm 3 Low
Set the low alarm set point for Output
3.
Process: range of sensor, if
[`SEN] is set to [``tc] or
[`rtd]
-1999 to 9999 if [`SEN] is
set to [`Ma], [uolt], or
[`Mu].
(-1999000 to 9999000)
32
*132, 133
R/W
If [Ot~3] is set to
[Pr;AL]