User guide

Watlow Series SD Limit 29 Chapter 5 Setup
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parentheses.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Note: Parameters appear in the Operations Page only if activated from the Programming Page.
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature parame-
ters are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.
[Addr]
[Addr]
Modbus Device Address
Set the device address for communica-
tions. Every controller on a network must
have a unique address.
1 to 247 1
This can
only be set
from the
controller
front
panel.
Output 2 is a communi-
cations output.
(SD_ _ - _ _ U _ - _ _ _ _ )
[bAud]
[bAud]
Baud Rate
Set the baud rate at which the communi-
cations occurs.
[9600]
[`19;2]
[`38;4]
[9600]
This can
only be set
from the
controller
front
panel.
Output 2 is a communi-
cations output.
(SD_ _ - _ _ U _ - _ _ _ _ )
[`LOC]
[ LOC]
Lockout
Set the security level for the user inter-
face.
Note: For FM Approval, the
[[~~LLOOCC]]
pa-
rameter must be set to 3 or the limit must
be remotely mounted to restrict casual ad-
justment of limit set points.
[```0]
(0) no lockout
[```1]
(1) Programming
Page locked and Setup
Page locked except for
[LOC]. [```2]
(2) Program-
ming Page locked and Set-
up Page locked except for
[LOC]. Limit set points are
the only Operation Page pa-
rameters accessible.
[```3]
(3) Full lockout. All
pages locked except for Set-
up Page,
[LOC] .
See the Features Chapter
for details.
[```0]
(0)
43 R/W
Always active.
[LdSP]
Lower Display Look
Selects what value appears in the lower
display.
[nonE]
None (0)
[Proc]
(1) Process Value
[L1;;Lo]
Limit 1 Low Set
Point (2)
[L1;hi]
Limit 1 High Set
Point (3)
[L2;Lo]
Limit 2 Low Set
Point (4)
[L2;hi]
Limit 2 High Set
Point (5)
[A2;Lo]
Alarm 2 Low Set
Point (6)
[A2;hi]
Alarm 2 High Set
Point (7)
[L3;Lo]
Limit 3 Low Set
Point (8)
[L3;hi]
Limit 3 High Set
Point (9)
[A3;Lo]
Alarm 3 Low Set
Point (10)
[A3;hi]
Alarm 3 High Set
Point (11)
[L1;hi]
(3)
45 R/W
Always active.