User guide

Watlow Series SD Limit 22 Chapter 3 Keys and Displays
Factory Page
[AMb] Ambient Temperature
[A;mn] Minimum Recorded Ambient Temperature
[A;ma] Maximum Recorded Ambient Temperature
[DSPL] Display Intensity
[rESt] Restore Factory Calibration
[Usr;r] Restore User Settings
[USr;S] Save User Settings
[dFLt] Default Parameters
[O;ty1] Output 1 Type
[O;ty2] Output 2 Type
[O;ty3] Output 3 Type
[`S;Id] Software ID
[S;UEr] Software Version
[S;bld] Software Build Number
[PWr] Power Type
[`Sn-] Serial Number 1
[`Sn_] Serial Number 2
[tc;50] Thermocouple, 50mV
[tc;00] Thermocouple, 0mV
[tc;32] Thermocouple, 32°F
[`r;15] RTD, 15 ohm
[r;380] RTD, 380 ohm
[``U;1] Input Calibrate, 1.0 Volt
[``U;9] Input Calibrate, 9.0 Volt
[``A;4] Input Calibrate, 4.0 mA
[`A;16] Input Calibrate, 16.0 mA
[03;1u] Output 3 Calibrate, 1.0 Volt
[03;9u] Output 3 Calibrate, 9.0 Volt
[03;4A] Output 3 Calibrate, 4.0 mA
[03;16] Output 3 Calibrate, 16.0 mA
Factory Page Overview
The Factory Page contains information on diagnostics,
calibration and restore-parameter functions.
To go to the Factory Page, press both the Up ¿ and
Down ¯ keys for six seconds from the Home Page.
Press the Advance Key to move through the pa-
rameter prompts.
Press the Up ¿ or Down ¯ keys to change the pa-
rameter value of Read/Write (R/W) parameters.
Press the RESET Key at any time to return to the
Home Page.
Note: Hardware configuration and programming selections deter-
mine what parameters appear in the Factory Page.
[FAct]
[page]
Programming Page Overview
The Programming Page determines what parameters
the user wants to appear in the Operations Page. Se-
lect a parameter for any of the 16 Programming Page
locations, P1 to P16. These now appear in the Opera-
tions Page. All 16 locations have parameters selected
as defaults.
To go to the Programming Page, hold down the RESET
key, then press the Advance Key , and hold both
down for about six seconds.
Press the Advance Key to move through the pa-
rameter prompts.
Press the Up ¿ or Down ¯ keys to change the pa-
rameter value.
Press the RESET Key at any time to return to the
Home Page.
Note: The hardware configuration and programming selections will
also determine what parameters appear in the Operations Page. A
Programming Page selection will not appear in the Operations
Page if the parameter is not active.
[Prog]
[PAgE]
Programming Page
[~~P1] Parameter Location 1 (48)
[~~P2] Parameter Location 2 (49)
[~~P3] Parameter Location 3 (50)
[~~P4] Parameter Location 4 (51)
[~~P5] Parameter Location 5 (52)
[~~P6] Parameter Location 6 (53)
[~~P7] Parameter Location 7 (54)
[~~P8] Parameter Location 8 (55)
[~~P9] Parameter Location 9 (56)
[~P10] Parameter Location 10 (57)
[~P11] Parameter Location 11 (58)
[~P12] Parameter Location 12 (59)
[~P13] Parameter Location 13 (60)
[~P14] Parameter Location 14 (61)
[~P15] Parameter Location 15 (62)
[~P16] Parameter Location 16 (63)
[nonE]
[``P1]
.
. (48)*.
.
[`P16]
(63)*
*Programming Page parameters Modbus register numbers
P1 through P16 are 48 through 63
Calibration information for the Series SD controllers is available
in pdf format. Go to www.watlow.com > Literature > Product