Instruction Manual

Watlow Series PD 95 Chapter 9 Device Config Table
Device Configuration > Outputs > Output 3
Output 3 - FunctionSelect the function of the output.,Configuration Output 3,,Off (0)Control (1)Event (2)Retransmit (3),Off (0),461 (R/W)
Output 3 - Output Cycle TimeSet the cycle time in seconds.,Configuration Output 3,,,,462 (R/W) (/10)
Output 3 - Control SourceSet Loop which will control this output.,Configuration Output 3,,Loop 1 (0)Loop 2 (1),Loop 1 (0),463 (R/W)
Output 3 - Output Mode Time BaseSelect method of output control as either Fixed Time Base or Variable Time Base.,Configuration Output
3,,Fixed (0)Variable (1),Fixed (0),466 (R/W)
Output 3 - StateDisplay state of output.,Monitor Device,,Inactive (0)Active (1),Inactive (0),467 (R)
Output 3 - Output DirectionSelect whether the output will be for heating (reverse action) or cooling (direct action).,Configuration Output
3,,Off (0)Heat (Indirect) (1)Cool (Direct) (2),Off (0),468 (R/W)
Output 3 - Logic OperatorSelect logic operation for event output.,Configuration Output 3,,And (0)Or (1),And (0),469 (R/W)
Output 3 - Output Source Alarm 1Set to enable Alarm 1 source.,Configuration Output 3,,No (0)Yes (1),No (0),470 (R/W)
Output 3 - Output Source Alarm 2Set to enable Alarm 2 source.,Configuration Output 3,,No (0)Yes (1),No (0),471 (R/W)
Output 3 - Output Source Alarm 3Set to enable Alarm 3 source.,Configuration Output 3,,No (0)Yes (1),No (0),472 (R/W)
Parameter Name
and Description
Web Page Your
Settings
Range Default Modbus*
(Read/write and
scaling)
Output 3 - Function
Select the function of the out-
put.
Configuration Output 3 Off (0)
Control (1)
Event (2)
Retransmit (3)
Off (0) 461 (R/W)
Output 3 - Output Cycle Time
Set the cycle time in seconds.
Configuration Output 3 0.1 to 60 seconds for non-
mechanical relay outputs
1.0 to 60 seconds for me-
chanical relay outputs
1.0 second for
non-mech
relay output
10.0 seconds
for mechanical
relay output
462 (R/W) (/10)
Output 3 - Control Source
Set Loop which will control
this output.
Configuration Output 3 Loop 1 (0)
Loop 2 (1)
Loop 1 (0) 463 (R/W)
Output 3 - Output Mode
Time Base
Select method of output con-
trol as either Fixed Time Base
or Variable Time Base.
Configuration Output 3 Fixed (0)
Variable (1)
Fixed (0) 466 (R/W)
Output 3 - Low Power Scale
Set unit value for low power
scale. This setting is the
process power value when the
analog output is at minimum.
Configuration Output 3 0 to 10000 %
(two decimal places)
10000 488-489 (R/W)
(/100)
Output 3 - High Power Scale
Set unit value for high power
scale. This setting is the
process power value when the
analog output is at maximum.
Configuration Output 3 0 to 10000 %
(two decimal places)
10000 490-491 (R/W)
(/100)
Output 3 - Output Direction
Select whether the output will
be for heating (reverse action)
or cooling (direct action).
Configuration Output 3 Off (0)
Heat (Indirect) (1)
Cool (Direct) (2)
Off (0) 468 (R/W)
Output 3 - Logic Operator
Select logic operation for
event output.
Configuration Output 3 AND (0)
OR (1)
And (0) 469 (R/W)
Output 3 - Output Source
Alarm 1
Set to enable Alarm 1 source.
Configuration Output 3 No (0)
Yes (1)
No (0) 470 (R/W)
Output 3 - Output Source
Alarm 2
Set to enable Alarm 2 source.
Configuration Output 3 No (0)
Yes (1)
No (0) 471 (R/W)
Output 3 - Output Source
Alarm 3
Set to enable Alarm 3 source.
Configuration Output 3 No (0)
Yes (1)
No (0) 472 (R/W)