Watlow Series PD ■ 82 ■ Chapter 9 Device Config Table
Device Configuration > Control Loops > Loop 1 > PID Set 5
Loop 1 - PID Set 5, Indirect Prop BandPID Set 5 - Set the heat (indirect) proportional band from set point in process units.,Configuration
Multiple PID Sets 1,,1000 to 999000,25000,743-744 (R/W) (/1000)
Loop 1 - PID Set 5, Indirect IntegralPID Set 5 - Set the heat (indirect) integral in minutes per repeat.,Configuration Multiple PID Sets 1,,0
to 99990,0,745-746 (R/W) (/1000)
Loop 1 - PID Set 5, Indirect DerivativePID Set 5 - Set the heat (indirect) derivative time in minutes.,Configuration Multiple PID Sets 1,,0 to
9990,0,747-748 (R/W) (/1000)
Loop 1 - PID Set 5, Indirect Dead BandPID Set 5 - Set the offset of the heat (indirect) proportional band from set point in process
units.,Configuration Multiple PID Sets 1,,0 to 999000,0,741-742 (R/W) (/1000)
Loop 1 - PID Set 5, Direct Prop BandPID Set 5 - Set the cool (direct) proportional band from set point in process units.,Configuration Multi-
ple PID Sets 1,,1000 to 999000,25000,751-752 (R/W) (/1000)
Loop 1 - PID Set 5, Direct IntegralPID Set 5 - Set the cool (direct) integral in minutes per repeat.,Configuration Multiple PID Sets 1,,0 to
99990,0,753-754 (R/W) (/1000)
Loop 1 - PID Set 5, Direct DerivativePID Set 5 - Set the cool (direct) derivative time in minutes.,Configuration Multiple PID Sets 1,,0 to
9990,0,755-756 (R/W) (/1000)
Loop 1 - PID Set 5, Direct Dead BandPID Set 5 - Set the offset of the cool (direct) proportional band from set point in process units.,Config-
uration Multiple PID Sets 1,,0 to 999000,0,749-750 (R/W) (/1000)
Parameter Name
and Description
Web Page Your
Settings
Range Default Modbus*
(Read/write and
scaling)
Loop 1 - PID Set 5 Indirect
Prop Band
Set the heat (indirect) propor-
tional band from set point in
process units.
Configuration Multiple
PID Sets 1
1000 to 999000 degrees or
units
25000 743-744 (R/W)
(/1000)
Loop 1 - PID Set 5 Indirect
Integral
Set the heat (indirect) integral
in minutes per repeat.
Configuration Multiple
PID Sets 1
0 to 99990 minutes 0 745-746 (R/W)
(/1000)
Loop 1 - PID Set 5 Indirect
Derivative
Set the heat (indirect) deriva-
tive time in minutes.
Configuration Multiple
PID Sets 1
0 to 9990 minutes 0 747-748 (R/W)
(/1000)
Loop 1 - PID Set 5 Indirect
Dead Band
Set the offset of the heat (indi-
rect) proportional band from
set point in process units.
Configuration Multiple
PID Sets 1
0 to 999000 degrees or units 0 741-742 (R/W)
(/1000)
Loop 1 - PID Set 5 Direct
Prop Band
Set the cool (direct) propor-
tional band from set point in
process units.
Configuration Multiple
PID Sets 1
1000 to 999000 degrees or
units
25000 751-752 (R/W)
(/1000)
Loop 1 - PID Set 5 Direct
Integral
Set the cool (direct) integral in
minutes per repeat.
Configuration Multiple
PID Sets 1
0 to 99990 minutes 0 753-754 (R/W)
(/1000)
Loop 1 - PID Set 5 Direct
Derivative
Set the cool (direct) derivative
time in minutes.
Configuration Multiple
PID Sets 1
0 to 9990 minutes 0 755-756 (R/W)
(/1000)
Loop 1 - PID Set 5 Direct
Dead Band
Set the offset of the cool (di-
rect) proportional band from
set point in process units.
Configuration Multiple
PID Sets 1
0 to 999000 degrees or units 0 749-750 (R/W)
(/1000)