Instruction Manual

Name and Descri
p
tion
Web Pa
ge
Ran
g
e
(
Scalin
g)
Iterations Default EIP Decimal
(
Hex
)
Modbus EIP Data T
y
p
e
A
cces
s
Analog Input {1 to 4} Counts
Displays the A-to-D counts for the corresponding
analog input.
Device Information 0 to 65,535
Analog Input 1
Analog Input 2
Analog Input 3
Analog Input 4
0
108/1/1 (6C/1/1)
108/1/2 (6C/1/2)
108/1/3 (6C/1/3)
108/1/4 (6C/1/4)
1001-1002
1003-1004
1005-1006
1007-1008
DINT R
Analog Out {1 to 4} Process Value
Displays the process output value for the
corresponding output.
Device Information
-30,000,000 to 30,000,000
(/1000)
Analog Output 1
Analog Output 2
Analog Output 3
Analog Output 4
0
108/1/13 (6C/1/D)
108/1/14 (6C/1/E)
108/1/15 (6C/1/F)
108/1/16 (6C/1/10)
1023-1024
1025-1026
1027-1028
1029-1030
DINT R
CJC Temperature {1 or 2}
Displays the cold junction compensation
tem
p
erature.
Device Information
32,000 to 167,000
(/1000)
108/1/9 (6C/1/9) 1015-1016 DINT R
Firmware Build
Indicates the firmware build number
.
0 to 32767 0 100/1/11 (64/1/B) 13 INT R
Number of Alarms Implemented
Indicates the number of alarms im
p
lemented
.
8 to 8 8 100/1/17 (64/1/11) 21 INT R
Number of Control Loops
Indicates the number of control loo
p
s
.
1 to 2 1 100/1/18 (64/1/12) 22 INT R
Bit Pattern 1
55 (hex) 55 (hex) 100/1/2 (64/1/2) 1 UINT R
Bit Pattern 2
AA (hex) AA (hex) 100/1/3 (64/1/3) 2 UINT R
ASCII '12
'
12 (ASCII) 12 (ASCII) 100/1/4 (64/1/4) 3 UINT R
ASCII '34
'
23 (ASCI) 23 (ASCI) 100/1/5 (64/1/5) 4 UINT R
Firmware ID
Indicates the firmware ID number
.
0 to 32,767 0 100/1/8 (64/1/8) 10 INT R
Firmware Branch
Indicates the firmware branch number
.
0 to 32,767 0 100/1/12 (64/1/C) 14 INT R
Number of Alarms Possible
Indicates the total number of alarms
.
8 to 8 8 Web page only Web page only R
Number of Possible Control Loops
Indicates the total number of control loo
p
s
.
1 to 2 1 Web page only Web page only R
Number of PID Sets Possible
Indicates the total number of PID sets
p
er loo
p.
1 to 5 5 Web page only Web page only R
Number of PID Sets Implemented
Indicates the number of PID sets im
p
lemented
.
1 to 5 5 100/1/19 (64/1/13) 23 INT R
Device Configuration > Network > TCP/IP Settings
Device Name
Specify the controller's name. The controller can
be browsed using this name via NetBIOS.
Network Configuration
PDxxxxxx
(
last six di
g
its o
f
serial number) 2
characters per word in
Modbus
108/1/49 (6C/1/31) 1179 SHORT_STRING R
Current Settings: IP Address
Indicates the current IP address.
Network Configuration
-2,147,483,647 to
2,147,483,647
1 245/1/5 (F5/1/5)
1st element of
STRUCT of
UDINT[5],
STRING
R
Current Settings: Subnet Mask
Indicates the current IP subnet mask.
Network Configuration
-2,147,483,647 to
2,147,483,647
1 245/1/5 (F5/1/5)
2nd element of
STRUCT of
UDINT[5],
STRING
R
Current Settings: Default Gateway
Indicates the current gateway IP address.
Network Configuration
-2,147,483,647 to
2,147,483,647
1 245/1/5 (F5/1/5)
3rd element of
STRUCT of
UDINT[5],
STRING
R
Current Settings: DNS Server
Indicates the current DNS server IP address.
Network Configuration
-2,147,483,647 to
2,147,483,647
1 245/1/5 (F5/1/5)
4th element of
STRUCT of
UDINT[5],
STRING
R
SERIES PD with EtherNet/IP
Addressing Information (rev c)
184