Instruction Manual
Name and Descri
p
tion
Web Pa
ge
Ran
g
e
(
Scalin
g)
Iterations Default EIP Decimal
(
Hex
)
Modbus EIP Data T
y
p
e
A
cces
s
Time Server Name
S
p
ecif
y
the real time server name
.
Clock Configuration 0 Web page only Web page only R/W
Time Server Fixed Address.
S
p
ecif
y
a fixed IP address for the time server
.
Clock Configuration
-2,147,483,647 to
2,147,483,647
1 Web page only Web page only R/W
Device Information
Universal Input {1 or 2} Type
Displays the type of hardware present for the
corres
p
ondin
g
analo
g
in
p
ut
.
Device Information
None (0)
Universal (1)
Analog Input 1
Analog Input 2
Universal (1)
None (0)
108/1/17 (6C/1/11)
108/1/18 (6C/1/12)
1043
1044
UINT R
Digital Input {3 or 4} Type
Displays the type or hardware present for the
corres
p
ondin
g
di
g
ital in
p
ut
.
Device Information
None (0)
Dry Contact (1)
Digital Input 3
Digital Input 4
None (0)
108/1/21 (6C/1/15)
108/1/22 (6C/1/16)
1047
1048
UINT R
Current Transformer Input {3 or 4} Type
Displays the type of hardware present for the
corres
p
ondin
g
analo
g
in
p
ut
.
Device Information
None (0)
Current Transformer (2)
CT Input 3
CT Input 4
None (0)
108/1/19 (6C/1/13)
108/1/20 (6C/1/14)
1045
1046
UINT R
Measured System Line Frequency
Dis
p
la
y
the measured line fre
q
uenc
y.
Device Information 0 to 32,767 60 108/1/32 (6C/1/20) 1076 INT R
Part Number
Indicates the controller's
p
art number
.
Device Information 12 Web page only Web page only R/W
MAC Address
Indicates the MAC address of the controller
.
Device Information 6 characters 0 246/1/3 (F6/1/3) N/A
STRUCT of
USINT[6]
R
Serial Number
Indicates the controller's serial number
.
Device Information 0 to 2000000200 0 100/1/6 (64/1/6) 7-8 DINT R
Date Code
Indicates the controller's date of manufacture
.
Device Information
-2,147,483,647 to
2,147,483,647
0 100/1/7 (64/1/7) 9 DINT R
Software Prototype Revision
Indicates the firmware
p
rotot
yp
e version
.
Device Information 0 to 32,767 0 100/1/10 (64/1/A) 12 INT R
Software Released Revision
Indicates the software revision
.
Device Information 0 to 32,767 0 100/1/9 (64/1/9) 11 INT R
Hardware - Net IP Resolution
Specify the order of methods to try to set the the
controller's IP address.
Configuration Network
DHCP, auto IP, fixed IP
(0)
DHCP, fixed IP (1)
Auto IP, fixed IP (2)
Fixed IP (3)
DHCP, auto IP,
fixed IP (0)
Web page only Web page only R/W
Number of Analog Inputs Implemented
Displays the number of analog inputs
im
p
lemented.
Device Information 1 to 4 1 100/1/14 (64/1/E) 18 INT R
Number of Digital Inputs Implemented
Displays the number of digital inputs implemented.
Device Information 0 to 2 0 100/1/15 (64/1/F) 19 INT R
Number of Outputs Implemented
Dis
p
la
y
s the number of out
p
uts im
p
lemented
.
Device Information 1 to 4 1 100/1/16 (64/1/10) 20 INT R
Number of Possible Analog Inputs
Displays the total number of analog inputs
available.
Device Information 1 to 4 1 Web page only Web page only R
Number of Possible Digital Inputs
Displays the total number of digital inputs
available.
Device Information 0 to 2 0 Web page only Web page only R
Number of Possible Outputs
Dis
p
la
y
s the total number of out
p
uts available
.
Device Information 1 to 4 1 Web page only Web page only R
Output {1 to 4} Type
Displays the type of hardware present for the
corresponding output.
Device Information
None (0)
Switched DC (1)
SSR (2)
Process (3)
Form A Relay (4)
Form C Relay (5)
Output 1
Output 2
Output 3
Output 4
Switched DC (1)
None (0)
None (0)
None (0)
108/1/23 (6C/1/17)
108/1/24 (6C/1/18)
108/1/25 (6C/1/19)
108/1/26 (6C/1/1A)
1049
1050
1051
1052
UINT R
SERIES PD with EtherNet/IP
Addressing Information (rev c)
183