Current Transformer Measurement Input
Select which current transformer input value this
alarm will monitor.
Alarm {1 to 8}
Configuration
Off (0)
CT Input 3 (2)
CT Input 4 (3)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
CT Input 4 (3)
105/1/4 (69/1/4)
105/2/4 (69/2/4)
105/3/4 (69/3/4)
105/4/4 (69/4/4)
105/5/4 (69/5/4)
105/6/4 (69/6/4)
105/7/4 (69/7/4)
105/8/4 (69/8/4)
534
548
562
576
590
604
618
632
UINT R/W
Current Transformer Alarm Set Point
Set the value that will trigger this alarm
Alarm {1 to 8}
Configuration
-30,000,000 to 30,000,000
(/1000)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
0
101/1/50 (65/1/32)
101/1/56 (65/1/38)
101/1/62 (65/1/3E)
101/1/68 (65/1/44)
101/1/74 (65/1/4A)
101/1/80 (65/1/50)
101/1/86 (65/1/56)
101/1/92 (65/1/5C)
108-109
121-122
134-135
147-148
160-161
173-174
186-187
199-200
DINT R/W
Send Email
Select to enable an email to be sent on activation
of alarm 1.
Alarm {1 to 8}
Configuration
No (0)
Yes (1)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
No (0) Web page only Web page only
Email Subject
Enter a subject for the alarm email.
Alarm {1 to 8}
Configuration
30 characters
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
0 Web page only Web page only
Alarm Hysteresis
Set how far the process value must return into the
normal operating range for an alarm to clear.
Alarm {1 to 8}
Configuration
0 to 30,000,000 (/1000)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
3,000
105/1/8 (69/1/8)
105/2/8 (69/2/8)
105/3/8 (69/3/8)
105/4/8 (69/4/8)
105/5/8 (69/5/8)
105/6/8 (69/6/8)
105/7/8 (69/7/8)
105/8/8 (69/8/8)
539-540
553-554
567-568
581-582
595-596
609-610
623-624
637-638
DINT R/W
Latching
Select whether this alarm will be latched, which
requires that it be cleared manually after the
process value returns to the normal range.
Alarm {1 to 8}
Configuration
No (0)
Yes (1)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
No (0)
105/1/7 (69/1/7)
105/2/7 (69/2/7)
105/3/7 (69/3/7)
105/4/7 (69/4/7)
105/5/7 (69/5/7)
105/6/7 (69/6/7)
105/7/7 (69/7/7)
105/8/7 (69/8/7)
538
552
566
580
594
608
622
636
UINT R/W