Heat (Indirect) Deadband
Set the offset of the heat (indirect) proportional
band from set point in process units.
Multiple PID Loop
{
1 or
2} Configuration
0 to 999,000 (/1000)
Loop 1 Set 1
Loop 1 Set 2
Loop 1 Set 3
Loop 1 Set 4
Loop 1 Set 5
Loop 2 Set 1
Loop 2 Set 2
Loop 2 Set 3
Loop 2 Set 4
Loop 2 Set 5
0
106/1/18 (6A/1/12)
106/1/26 (6A/1/1A)
106/1/34 (6A/1/22)
106/1/42 (6A/1/2A)
106/1/50 (6A/1/32)
106/2/18 (6A/2/12)
106/2/26 (6A/2/1A)
106/2/34 (6A/2/22)
106/2/42 (6A/2/2A)
106/2/50 (6A/2/32)
677-678
693-694
709-710
725-726
741-742
797-798
813-814
829-830
845-846
861-862
DINT R/W
Cool (Direct) Propband
Set the cool (direct) proportional band in process
units.
Multiple PID Loop
{
1 or
2} Configuration
1,000 to 999,000 (/1000)
Loop 1 Set 1
Loop 1 Set 2
Loop 1 Set 3
Loop 1 Set 4
Loop 1 Set 5
Loop 2 Set 1
Loop 2 Set 2
Loop 2 Set 3
Loop 2 Set 4
Loop 2 Set 5
25,000
106/1/23 (6A/1/17)
106/1/31 (6A/1/1F)
106/1/39 (6A/1/27)
106/1/47 (6A/1/2F)
106/1/47 (6A/1/2F)
106/2/23 (6A/2/17)
106/2/31 (6A/2/1F)
106/2/39 (6A/2/27)
106/2/47 (6A/2/2F)
106/2/55 (6A/2/37)
687-688
703-704
719-720
735-736
751-752
807-808
823-824
839-840
855-856
871-872
DINT R/W
Cool (Direct) Integral
Set the cool (direct) integral in minutes per repeat.
Multiple PID Loop
{
1 or
2} Configuration
0 to 99,990 (/1000)
Loop 1 Set 1
Loop 1 Set 2
Loop 1 Set 3
Loop 1 Set 4
Loop 1 Set 5
Loop 2 Set 1
Loop 2 Set 2
Loop 2 Set 3
Loop 2 Set 4
Loop 2 Set 5
0
106/1/24 (6A/1/18)
106/1/32 (6A/1/20)
106/1/40 (6A/1/28)
106/1/48 (6A/1/30)
106/1/56 (6A/1/38)
106/2/24 (6A/2/18)
106/2/32 (6A/2/20)
106/2/40 (6A/2/28)
106/2/48 (6A/2/30)
106/2/56 (6A/2/38)
689-690
705-706
721-722
737-738
753-754
809-810
825-826
841-842
857-858
873-874
DINT R/W
Cool (Direct) Derivative
Set the cool (direct) derivative time in minutes.
Multiple PID Loop
{
1 or
2} Configuration
0 to 9,990 (/1000)
Loop 1 Set 1
Loop 1 Set 2
Loop 1 Set 3
Loop 1 Set 4
Loop 1 Set 5
Loop 2 Set 1
Loop 2 Set 2
Loop 2 Set 3
Loop 2 Set 4
Loop 2 Set 5
0
106/1/25 (6A/1/19)
106/1/33 (6A/1/21)
106/1/41 (6A/1/29)
106/1/49 (6A/1/31)
106/1/57 (6A/1/39)
106/2/25 (6A/2/19)
106/2/33 (6A/2/21)
106/2/41 (6A/2/29)
106/2/49 (6A/2/31)
106/2/57 (6A/2/39)
691-692
707-708
723-724
739-740
755-756
811-812
827-828
843-844
859-860
875-876
DINT R/W
Cool (Direct) Deadband
Set the offset of the cool (direct) proportional band
from set point in process units.
Multiple PID Loop
{
1 or
2} Configuration
1,000 to 999,000 (/1000)
Loop 1 Set 1
Loop 1 Set 2
Loop 1 Set 3
Loop 1 Set 4
Loop 1 Set 5
Loop 2 Set 1
Loop 2 Set 2
Loop 2 Set 3
Loop 2 Set 4
Loop 2 Set 5
0
106/1/22 (6A/1/16)
106/1/30 (6A/1/1E)
106/1/38 (6A/1/26)
106/1/46 (6A/1/2E)
106/1/54 (6A/1/36)
106/2/22 (6A/2/16)
106/2/30 (6A/2/1E)
106/2/38 (6A/2/26)
106/2/46 (6A/2/2E)
106/2/54 (6A/2/36)
685-686
701-702
717-718
733-734
749-750
805-806
821-822
837-838
853-854
869-870
DINT R/W
Cross Over Point 1
Set value to switch from PID set 1 to PID set 2
.
Multiple PID Loop
{
1 or
2} Configuration
-30,000,000 to 30,000,000
(/1000)
Loop 1
Loop 2
30,000,000
106/1/14 (6A/1/E)
106/2/14 (6A/2/E)
669-670
789-790
DINT R/W
Cross Over Point 2
Set value to switch from PID set 2 to PID set 3
.
Multiple PID Loop
{
1 or
2} Configuration
-30,000,000 to 30,000,000
(/1000)
Loop 1
Loop 2
30,000,000
106/1/15 (6A/1/F)
106/2/15 (6A/2/F)
671-672
791-792
DINT R/W
SERIES PD with EtherNet/IP
Addressing Information (rev c)
176