Instruction Manual
Name and Descri
p
tion
Web Pa
ge
Ran
g
e
(
Scalin
g)
Iterations Default EIP Decimal
(
Hex
)
Modbus EIP Data T
y
p
e
A
cces
s
High Current Scale
Set the input process current
(
in milliamps
)
that wil
l
corres
p
ond to the Hi
g
h Process Scale
.
Analog Input {1 or 2}
Configuration
0 to 20,000 (/1000)
Analog Input 1
Analog Input 2
20000
102/1/5 (66/1/5)
102/2/5 (66/2/5)
256-257
286-287
DINT R/W
Temperature Process Value Units
Indicates the temperature units displayed in the
web pages for a thermocouple and RTD input.
This can be set in the web
p
a
g
e
.
Analog Input {1 or 2}
Configuration
Fahrenheit (0)
Celsius (1)
Analog Input 1
Analog Input 2
Fahrenheit (0)
108/1/35 (6C/1/23)
108/1/39 (6C/1/27)
1109
1120
UINT R
Temperature Process Value Precision
Indicates the number of decimal places displayed
in the web pages for a thermocouple or RTD input.
This can be set in the web
p
a
g
e
.
Analog Input {1 or 2}
Configuration
0 (0)
0.0 (1)
Analog Input 1
Analog Input 2
0 (0)
108/1/33 (6C/1/21)
108/1/37 (6C/1/25)
1107
1118
UINT R
Filter Method
Select a filter method to smooth out a rapidly
chan
g
in
g
in
p
ut si
g
nal
.
Analog Input {1 or 2}
Configuration
Off (0)
First Order (1)
Analog Input 1
Analog Input 2
Off (0)
102/1/11 (66/1/B)
102/2/11 (66/2/B)
268
298
UINT R/W
Filter Time Base
Set the filter time. A higher value will smooth out
the si
g
nal more.
Analog Input {1 or 2}
Configuration
100 to 60,000 (/1000)
Analog Input 1
Analog Input 2
100
102/1/12 (66/1/C)
102/2/12 (66/2/C)
269-270 DINT R/W
Single Offset Value
Set a value to compensate for the input's lead
resistance and sensor inaccurac
y.
Analog Input {1 or 2}
Configuration
-9,999,000 to 9,999,000
(/1000)
Analog Input 1
Analog Input 2
0
102/1/10 (66/1/A)
102/2/10 (66/2/A)
266-267
296-297
DINT R/W
Device Configuration > Inputs > CT Input {3 or 4}
Function
Set whether to enable the CT in
p
ut
.
CT Input {3 or 4}
Configuration
Off (0)
CT Current (6)
CT Input 3
CT Input 4
Off (0)
102/3/1 (66/3/1)
102/4/1 (66/4/1)
311
331
UINT R/W
CT Precision
Indicates the number of decimal places displayed
in the web page for CT inputs. This can be set in
the web
p
a
g
e
.
CT Input {3 or 4}
Configuration
0 (0)
0.0 (1)
0.00 (2)
0.000 (3)
CT Input 3
CT Input 4
0 (0)
108/1/42 (6C/1/2A)
108/1/46 (6C/1/2E)
1124
1128
UINT R
CT Units
Indicates the units displayed in the web page for
CT in
p
uts. This can be set in the web
p
a
g
e
CT Input {3 or 4}
Configuration
Up to four alphanumeric
characters
CT Input 3
CT Input 4
108/1/44 (6C/1/2C)
108/1/48 (6C/1/30)
1125-1126
1129-1130
SHORT_STRING R
Low CT Scale
Set the value that will be displayed when the
current transformer (CT) input is at its minimum,
as determined by the Low Current Scale.
CT Input {3 or 4}
Configuration
-30,000,000 to 30,000,000
(/1000)
CT Input 3
CT Input 4
-30,000,000
102/3/8 (66/3/8)
102/4/8 (66/4/8)
316-317
336-337
DINT R/W
High CT Scale
Set the value that will be displayed when the
current transformer (CT) input is at its maximum,
as determined by the High Current Scale.
CT Input {3 or 4}
Configuration
-30,000,000 to 30,000,000
(/1000)
CT Input 3
CT Input 4
30,000,000
102/3/9 (66/3/9)
102/4/9 (66/4/9)
318-319
338-339
DINT R/W
Low Current Scale
Set the input process current
(
in milliamps
)
that wil
l
corres
p
ond to the Low CT Scale
.
CT Input {3 or 4}
Configuration
0 to 50,000 (/1000)
CT Input 3
CT Input 4
0
102/3/4 (66/3/4)
102/4/4 (66/4/4)
312-313
332-333
DINT R/W
High Current Scale
Set the input process current
(
in milliamps
)
that wil
l
corres
p
ond to the Hi
g
h CT Scale
.
CT Input {3 or 4}
Configuration
0 to 50,000 (/1000)
CT Input 3
CT Input 4
20,000
102/3/5 (66/3/5)
102/4/5 (66/4/5)
314-315
334-335
DINT R/W
Output
Select output to monitor with the CT input.
CT Input {3 or 4}
Configuration
Output 1 (0)
Output 2 (1)
Output 3 (2)
Output 4 (3)
CT Input 3
CT Input 4
Output 2 (1)
102/3/13 (66/3/D)
102/4/13 (66/4/D)
322
342
UINT R/W
Single Offset Value
Set a value to compensate for the input's lead
resistance and si
g
nal inaccurac
y.
CT Input {3 or 4}
Configuration
-9,999,000 to 9,999,000
(/1000)
CT Input 3
CT Input 4
0
102/3/10 (66/3/A)
102/4/10 (66/4/A)
320-321
340-341
DINT R/W
SERIES PD with EtherNet/IP
Addressing Information (rev c)
172