Instruction Manual
Name and Descri
p
tion
Web Pa
ge
Ran
g
e
(
Scalin
g)
Iterations Default EIP Decimal
(
Hex
)
Modbus EIP Data T
y
p
e
A
cces
s
Alarm Status
Indicates the status of the Alarm.
Monitor Device
Inactive or Off (0)
Active (1)
Silenced (2)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
Inactive or Off (0)
101/1/47 (65/1/2F)
101/1/53 (65/1/35)
101/1/59 (65/1/3B)
101/1/65 (65/1/41)
101/1/71 (65/1/47)
101/1/77 (65/1/4D)
101/1/83 (65/1/53)
101/1/89 (65/1/59)
103
116
129
142
155
168
181
194
UINT R
Latching Action
Select to clear a latched alarm after the process
value returns to normal.
Monitor Device
No (0)
Yes (1)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
No (0)
101/1/52 (65/1/34)
101/1/58 (65/1/3A)
101/1/64 (65/1/40)
101/1/70 (65/1/46)
101/1/76 (65/1/4C)
101/1/82 (65/1/52)
101/1/88 (65/1/58)
101/1/94 (65/1/5E)
111
124
137
150
163
176
189
202
UINT R/W
Silence Action
Select to silence an alarm.
Monitor Device
No (0)
Yes (1)
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
No (0)
101/1/51 (65/1/33)
101/1/57 (65/1/39)
101/1/63 (65/1/3F)
101/1/69 (65/1/45)
101/1/75 (65/1/4B)
101/1/81 (65/1/51)
101/1/87 (65/1/57)
101/1/93 (65/1/5D)
110
123
136
149
162
175
188
201
UINT R/W
Analog Input {1 or 2} - Filtered Process Value
Indicates the filtered process value measured by
the corresponding analog input.
Monitor Device
-30,000,000 to 30,000,000
(/1000)
Analog Input 1
Analog Input 2
101/1/2 (65/1/2)
101/1/7 (65/1/7)
33-34
45-46
DINT R
Analog Input {1 or 2} - Process Value
Indicates the unfiltered process value measured b
y
the corres
p
ondin
g
analo
g
in
p
ut
.
Monitor Device
-30,000,000 to 30,000,000
(/1000)
Analog Input 1
Analog Input 2
101/1/1 (65/1/1)
101/1/6 (65/1/6)
31-32
43-44
DINT R
CT Input {3 or 4} - Filtered Process Value
Indicates the filtered process value measured by
the corres
p
ondin
g
analo
g
in
p
ut
.
Monitor Device
CT Input 3
CT Input 4
Web page only Web page only
CT Input {3 or 4} - Process Value
Indicates the unfiltered process value measured b
y
the corres
p
ondin
g
analo
g
in
p
ut
.
Monitor Device
CT Input 3
CT Input 4
Web page only Web page only
Alarm Latching / Silence Action
Set the coresponding bit to clear a latched alarm.
Bits 1 through 8 correspond to alarms 1 to 8.
Monitor Device -32,768 to 32,767 0 101/1/100 (65/1/64) WORD R/W
Alarm Status
Read the corresponding bit to determine the alarm
status. 0 = inactive, 1 = active. Bits 1 to 8
corres
p
ond to alarms 1 to 8
.
Monitor Device -32,768 to 32,767 0 101/1/98 (65/1/62) WORD R
Analog Input Failure Latching Acknowledge
Set the correspondin
g
bit to acknowled
g
e the input
error. 1 = acknowledge. Bit 1 corresponds to
analog input 1 and bit 2 corresponds to analog
input 2.
Monitor Device -32,768 to 32,767 0 101/1/99 (65/1/63) WORD R/W
Control Power Output
Monitor Device -10000 to 10000 (/100)
Loop 1
Loop 2
0 101/1/96 (65/1/60) INT R
SERIES PD with EtherNet/IP
Addressing Information (rev c)
170