Instruction Manual

Watlow Series PD 99 Chapter 9 Device Config Table
Parameter Name
and Description
Web Page Your
Settings
Range Default Modbus*
(Read/write and
scaling)
Output 4 - Output Source Alarm 4Set to enable Alarm 4 source.,Configuration Output 4,,No (0)Yes (1),No (0),513 (R/W)
Output 4 - Output Source Alarm 5Set to enable Alarm 5 source.,Configuration Output 4,,No (0)Yes (1),No (0),514 (R/W)
Output 4 - Output Source Alarm 6Set to enable Alarm 6 source.,Configuration Output 4,,No (0)Yes (1),No (0),515 (R/W)
Output 4 - Output Source Alarm 7Set to enable Alarm 7 source.,Configuration Output 4,,No (0)Yes (1),No (0),516 (R/W)
Output 4 - Output Source Alarm 8Set to enable Alarm 8 source.,Configuration Output 4,,No (0)Yes (1),No (0),517 (R/W)
Output 4 - Output LogicSelect output state in an alarm true condition.,Configuration Output 4,,Energized (0)De-energized (1),Energized
(0),518 (R/W)
Output 4 - Low Power Scale,Configuration Output 4,,0 to 10000,0,519-520 (R/W) (/100)
Output 4 - High Power Scale,Configuration Output 4,,0 to 10000,10000,521-522 (R/W) (/100)
Output 4 - Output Source Digital 3Set to enable Digital Input 3 source.,Configuration Output 4,,No (0)Yes (1),No (0),523 (R/W)
Output 4 - Output Source Digital 4Set to enable Digital Input 4 source.,Configuration Output 4,,No (0)Yes (1),No (0),524 (R/W)
Output 4 - Output Source
Alarm 1
Set to enable Alarm 1 source.
Configuration Output 4 No (0)
Yes (1)
No (0) 510 (R/W)
Output 4 - Output Source
Alarm 2
Set to enable Alarm 2 source.
Configuration Output 4 No (0)
Yes (1)
No (0) 511 (R/W)
Output 4 - Output Source
Alarm 3
Set to enable Alarm 3 source.
Configuration Output 4 No (0)
Yes (1)
No (0) 512 (R/W)
Output 4 - Output Source
Alarm 4
Set to enable Alarm 4 source.
Configuration Output 4 No (0)
Yes (1)
No (0) 513 (R/W)
Output 4 - Output Source
Alarm 5
Set to enable Alarm 5 source.
Configuration Output 4 No (0)
Yes (1)
No (0) 514 (R/W)
Output 4 - Output Source
Alarm 6
Set to enable Alarm 6 source.
Configuration Output 4 No (0)
Yes (1)
No (0) 515 (R/W)
Output 4 - Output Source
Alarm 7
Set to enable Alarm 7 source.
Configuration Output 4 No (0)
Yes (1)
No (0) 516 (R/W)
Output 4 - Output Source
Alarm 8
Set to enable Alarm 8 source.
Configuration Output 4 No (0)
Yes (1)
No (0) 517 (R/W)
Output 4 - Output Logic
Select output state in an
alarm true condition.
Configuration Output 4 Energized (0)
De-energized (1)
Energized (0) 518 (R/W)
Output 4 - Output Source Digi-
tal 3
Set to enable Digital Input 3
source.
Configuration Output 4 No (0)
Yes (1)
No (0) 523 (R/W)
Output 4 - Output Source Digi-
tal 4
Set to enable Digital Input 4
source.
Configuration Output 4 No (0)
Yes (1)
No (0) 524 (R/W)
Output 1-4 - Expected System
Line Frequency
Set the line frequency of the
input power if the zero cross
detection circuit fails.
Configuration Output 1
Configuration Output 2
Configuration Output 3
Configuration Output 4
50 Hz (0)
60 Hz (1)
60 Hz (0) 1075 (R/W)