Owner manual

Watlow Series N7 21 Appendix
Appendix
A
Specifications
Controller
Up to four sensor inputs, eight switched dc outputs, eight dc
inputs, two process outputs
Battery backed, real-time clock
One non-isolated slave communications channel
One non-isolated master communications channel
Optional ethernet communications module
Optional high-voltage output module
Operator Interface
Four-character, 0.56-inch, seven-segment display
Eight-character, 0.2 inch, alphanumeric display
Overlay interface supports up to 32 keys and LED indicator
lights
Overlay interface
Switch closed input < 100
Switch open input > 100 k
LED current limiting resistor: 200
LED supply voltage: 5V
Operating Environment
•0 to 80°C (32 to 176°F) @ 0 to 90% RH, non-condensing
Standard Conditions For Specifications
Ambient temperature 25°C (77°F) ±3°C, 24VÅ (ac), 50 to 60 Hz
Configured Sensor Inputs
Update rate: 5Hz
Thermocouple
Multiple channel applications require at least one ungrounded
thermocouple.
Input current: 0.5 nA
Maximum source resistance: 20
Accuracy: ± 1.1°C (2°F)
Drift: ± 0.10°C/°C (± 0.10°F/°F)
Input ranges:
Type J: -46 to 316°C (-50 to 600°F)
Type K: -46 to 316°C (-50 to 600°F)
RTD
2- or 3-wire platinum
DIN curve (.00385 curve)
700 µA maximum excitation current
Accuracy: ± 1.1°C (2°F)
Drift: ± 0.10°C/°C (± 0.10°F°/F)
Range: -46 to 316°C (-50 to 600°F)
Voltage
Input impedance 60 k
Input range: 0 to 12V
Accuracy: ± 25 mV
Drift: ± 5mV/F
Current
Input impedance 100
Input range: 0 to 22mA
Accuracy: ± 40 µA
Drift: ± 5 µA/F
Event Input
Input high: 3 to 30V or >10 k
Input low: -0.5 to 0.5V or < 250
Outputs
Switched DC Outputs
5V at 30mA maximum
Voltage Output
Range: 0 to 12V at 20 mA maximum
Minimum: load impedance 500
Accuracy: ± 100mV
Drift: ± 2.1mV/F
Current Output
Range 0 to 22mA at 20V maximum
Maximum load impedance 1,000
Accuracy: ± 100µA
Drift: ± 4.3µA/F
Agency
•UL60730, c-UL File E43684
EU LV Directive 72/23/EEC EN 60730
EU EMC Directive 89/336/EEC
emissions
immunity
NSF Option, File 49660-0003-000
NAFEM Communications/Evaluate proper listing
CSA standard E60730-2-9
Power/Line Voltage
24 VÅ (ac) power input (20.4 to 26.4Å (ac)), Class 2 power
source required
47 to 63 Hz
15VA maximum
Program retention upon power failure via non-volatile memory
Battery/real time clock option: six-year lithium battery, pro-
vides power upon backup power failure, operation resumption
after power recovery, ability to display time.
Audible Alarm
Internal audible alarm, 85 dB @ 10cm @ 2 KHz. Output fre-
quencies supported: 250, 500, 1,000, 2,000, 4,000 Hz.
Storage Temperature
-40 to 80°C (-40 to 176°F)
Optional High-Voltage Board
Optional high-voltage board will have six outputs, either solid-
state relay, electromechanical relay or no-arc relay
Relay Specification:
Contact type: normally open
Maximum operating current: 8 A
Maximum operating voltage: 250VÅ (ac)
Pilot duty: 250 VA