Chapter 3: Communicating by DeviceNet Series D8 User’s Guide
74 Watlow Anafaze Doc. 0600-3120-2000
Table 3.35 Ratio Instance Attributes
(Instances 1 to 4 or 8)
NOTE! All successful explicit message responses
from a Set service will contain no data. The
response will be a two-byte message con-
taining the requester’s node address and
service code (with R/R bit set).
Cascade Object
The Cascade Object provides read/write access to all cascade 
parameters. Instance 0 of this object contains the class at-
tributes listed in Table 3.37. The four-loop controller has four 
additional instances, and the eight-loop controller has eight 
additional instances, each containing the attributes listed in 
Table 3.38. Instance 1 corresponds to loop 1, instance 2 cor-
responds to loop 2, and so on.
Table 3.36 Cascade Class and Services
Table 3.37 Cascade Class Attributes
(Instance 0)
Attribute Access  Name Type Description
100 (64 hex) Get/Set  Ratio Master Loop USINT  See page 150.
101 (65 hex) Get/Set  Ratio Low Set Point INT  See page 150.
102 (66 hex) Get/Set  Ratio High Set Point INT  See page 151.
103 (67 hex) Get/Set  Control Ratio UINT  See page 151.
104 (68 hex) Get/Set  Ratio Set Point Differential INT  See page 151.
Class Code 6A hex
Class Services 0E hex Get Attribute Single
Instance Services
0E hex Get Attribute Single
10 hex Set Attribute Single
Attribute Access Name Type Description
1 (1 hex) Get  Revision  UINT  Revision of this object 
2 (2 hex) Get 
Max 
Instance 
UINT  Maximum instances of this object (8)
3 (3 hex) Get 
Number of
Instances 
UINT  Number of object instances 